6
IQ41x Installation Instructions - Configuring TG201251 Issue 5, 22-Aug-2014
IQ41x
InstallationInstructions-Configuring
19
Set up Baud Rate
(if current loop network being used with Lan of IQ4s only)
2
ConFIguRAtIonPRoCeDuRe
(continued)
It is necessary for one IQ4 to be set to a specific baud rate to
ensure the other IQ4s select the required baud rate.
Use SET’s IQTool Monitor Applet to disable autobaud and
specify the baud rate.
Module Parameter
Range
IQ Lan
network
Autobaud
0 or 1. 0=Disabled
Baud Rate
1k2, 4k8, 9k6, 19k2, 38k4
IQTool Monitor Applet Manual (TE201298)
20
SetupAdditionaltrendAddressing
(if required)
IQTool Monitor Applet Manual (TE201298)
If the IQ41x is to provide a network connection for supervisors
and tools setup the Supervisor Port and USB Engineering
Port as required.
Use SET’s IQTool Monitor Applet to set the Supervisor Port or
USB Engineering Port as required.
Module Parameter
Range
Address Supervisor port
0, 4 to 9, 11 to 119
Default=0 local access only
USB
Engineering port
0, 4 to 9, 11 to 119
Default=0 temporarily takes
address 125
n
q
4
e
y
e
c
p
4
1
2
3
4
5
Q411B_V53440388
O/S
00:10:70:0D:1E:92
MAC Addr
IQ411-1010U5000
Part No:
LAN
4
IP
Addr
18
WriteDetailsonLabel
O/S
Lan
Fixed IP Address
or Hostname (if DCHP)
Draft