Set up Ethernet Access Across Routers 

(if required)

If the Lan is to be built across a router(s) details of devices 

(on  each  subnet)  must  be  specified  to  enable  cross-router 

communications.

Use IP Tool – see step 13 – to specify IP settings for up to 20 

devices in the Remote Trend Devices list:

Parameter

Value

IP Address

If using dynamic (DHCP) addressing:

Enter the host name of the remote device.

If using static (fixed) addressing:

Enter the IP Address of the remote device, 

in the format:  xxx.xxx.xxx.xxx

Subnet Mask

The subnet mask for the remote device, in 

the format: xxx.xxx.xxx.xxx

IP Tool Manual (TE200638)

17

SetuptrendAddressing

SingleIQ4orLanofIQ4sonethernet:

 

Use IP Tool – see step 13 – to set the address (ensuring it 

is unique on the Lan) and Lan number

IQ4s are given an address and Lan number in the factory. The 

address is set in the range 11 to 119 on a rolling basis with the 

Lan number set to 20. Therefore it may be necessary to set up 

the address/Lan number as required. 

Parameter

Range

Description

Address

1, 4 to 9, 11 to 

119

Must be unique on Lan

Lan 

number

1, 4 to 9, 11 to 

119

Must  be  the  same  as  all 

devices it is to form a Lan with.

Note: Changing the Lan number and address will cause the 

IQ4 to reset.

IP Tool Manual (TE200638)

IQTool  Addresser  Applet  Manual 

(TE201299)

LanofIQ4soncurrentloop:

 

Run SET, right click the Lan of IQ4s in the 

System View

 

select 

Address IQ4 Device

 to run the IQTool Addresser 

Applet, and click   to run the Discovery Wizard.

 

Select  either  ‘Automatic  Discovery’  (recommended)  or 

‘Manual Discovery’. If ‘Automatic Discovery’ was selected 

you should also select Duplicate Address Resolution.

Automatic Discovery: 

The tool will discover the devices, 

and attempt to resolve duplicate addresses.

Manual Discovery: 

Scan  the  bar  code,  or  press  the 

Service Button for each controller.

WARNING 

For  /230  options  hazardous 

voltages exist when the unit is powered. Take 

suitable precautions.

 

If  the  Lan  is  not  as  expected  it  could  be  because  of 

installation  related  reasons,  e.g.  wiring  faults,  power 

failure etc. Check the devices are operating correctly and 

repeat discovery. If there are duplicate addresses add the 

devices to the grid manually, using network address and 

serial number. If necessary use SET’s System View to set 

the Lan number, and IQTool to set the address.

LanIQ4andpreIQ4controllersoncurrentloop:

 

Run  SET,  right  click  the  Lan  of  IQ4s  in  the 

System 

View 

and select 

Address IQ4 Device

 to run the IQTool 

Addresser Applet.

 

Add the IQ4 to the grid manually by clicking  , specifying 

the serial number, and address, and clicking  .

 

Use SET’s System View to set the Lan number.

It is recommended that at least two devices from each subnet 

are  specifed.  For  increased  reliability  details  of  additional 

devices should be specified. 

If static IP addressing is being used the list should contain the 

devices with the lowest IP addresses. 

The same list must be copied to other EINC type devices on 

the network. 

Hint: Ticking the check box next to the Remote Trend Devices 

list retains the list in IP Tool, allowing it to be easily copied to 

other devices:

2

ConFIguRAtIonPRoCeDuRe

(continued)

Draft

Summary of Contents for IQ41 Series

Page 1: ...Applet Manual TE201298 IQTool Addresser Applet Manual TE201299 IQ4 Configuration Manual TE201263 Note PDF copies are included with SET installation in the following folder C Trend Control Systems Docu...

Page 2: ...Re continued Serial Number n q 4 e y e c p 4 1 2 3 4 5 Q411B_V53440388 O S Q411B_V53440388 n q 4 e y e c p 4 1 2 3 4 5 00 10 70 0D 1E 92 MAC Addr IQ411 1010U5000 Part No LAN 4 MAC Addr IP Addr LAN Loc...

Page 3: ...d 22 23 24 25 RX 28 29 WMB RX TX TX RX OK 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 1 2 3 230V 19 4 5 10 24V 0V 0V 0V 0V 0V 0V 9 8 6 7 1 2 3 Watchdog red Power green 11 Check ethernet LeDs if Ethernet is...

Page 4: ...addressing the unit automatical obtains its IP addressing details IP address subnet mask default router WINS server and DNS server from the network s DHCP Dynamic Host Configuration Protocol server I...

Page 5: ...run the IQTool Addresser Applet and click to run the Discovery Wizard Select either Automatic Discovery recommended or Manual Discovery If Automatic Discovery was selected you should also select Dupl...

Page 6: ...IQTool Monitor Applet Manual TE201298 20 Set up Additional Trend Addressing if required IQTool Monitor Applet Manual TE201298 If the IQ41x is to provide a network connection for supervisors and tools...

Page 7: ...nd switch off all other devices on the network If still OFF check network cabling for short circuits with a multimeter NOT Megger If ON switch on other devices until faulty device found i e OK LED goe...

Page 8: ...9k6 Note SET will set up the controller s date and time to that of the PC during download However they may be set up from a controller configured as timemaster Configure the strategy using SET and te...

Page 9: ...supervisors tools and displays as described in Connect to IQ4 on page 10 Connection of PCs displays etc can be made directly to controller via the RS232 Local supervisor Port USB Local Engineering Por...

Page 10: ...o IQ4 can be made directly via the RS232 Local Supervisor Port USB Local Engineering Port or Ethernet Port Connection can also be made over a network Ethernet Connection use Notes IPTool SET Web Brows...

Page 11: ...vice on the same Ethernet Trend network Note If connecting with IP Tool the PC should be on the same Ethernet segment as the IQ4 Note To make a connection with a web browser use IQ4 s IP address or ho...

Page 12: ...r steps 1 to 5 of the Installation Configuring section 5 DISPoSAL WEEE Directive At the end of their useful life the packaging and product should be disposed of by a suitable recycling centre Do not d...

Reviews: