One group of user codes can be programmed to operate output 1 for door open. The following are
the programming procedures.
Loca�ons
User ID Entry of Code
Confirm
Output 1
00 - 99 4 -8 Digits
NOTE:
●
Loca�on 1 is the storage place for the User Codes for Output 1.
●
100 unique User IDs
00-99
for 100 User Codes.
●
The user codes can be 4-8 digits long in manual code entry mode; but must have the same length
as the master code if the keypad is in auto code entry mode.
●
See “Programming Summary Chart” Sec�on C – 1 for more informa�on
●
See informa�on on
Loca�on 82
concerning digit length in Auto and Manual code entry modes.
Programming Example :
1. Set keypad to programming mode with master code and
key. Taking the previous programmed
master code
3 2 8 9
as example here:
2. Program an User Code 8 3 2 1 for output 1 ---------- One of the 100 user codes (user ID: 00-99,
taking ID = 01 as example):
3. Exit programming mode by pressing the
Operation (Manual Code Entry Mode)
Press
---------- Output 1 ac�vates (The door is open)
NOTE:
In Auto Code Entry Mode only the User Codes that have the same digit length as the master code are
valid and press the
key is not required.
Programming The User Codes
(Loca�on 1)
Most of the keypads mainly controls “Going In” with user codes and controls “Going Out” simply
pressing an egress bu�on. However, in some situa�ons, providing some warning and delay are
desirable before the door is open a�er pressing the egress bu�on. For example, in hospitals or
schools, it may be desirable to delay the egress opera�on and provide a warning to prevent pa�ents
or young children from easily leaving the protected area.
●
An egress bu�on programmed with egress delay & warning does not affect the normal opera�on
of the keypad. The user codes are always the first priority to operate output 1 to actuate the door
lock.
●
It is not necessary to do anything if egress delay is not required. Just leave the egress bu�on on its
default se�ng.
Loca�ons
Egress Modes
Confirm
0 to 4
The Five Egress Modes:
--
Momentary Contact with no warning and delay
(Default)
Press the egress bu�on momentarily, Output 1 ac�vates instantly to open the door.
--
Momentary Contact with 5 seconds delay and warning beep
Press the egress bu�on momentarily, the keypad will beep for 5 seconds before Output 1
ac�vates.
--
Momentary Contact with 10 seconds delay and warning beep
Press the egress bu�on momentary, the keypad will beep for 10 seconds before Output 1
ac�vates.
--
Hold contact for 5 seconds with warning beep
Press and hold the egress bu�on for 5 seconds and the keypad will beep for those 5 seconds
before Output 1 ac�vates.
--
Hold contact for 10 seconds with warning beep
Press and hold the egress bu�on for 10 seconds and the keypad will beep for those 10
seconds before Output 1 ac�vates.
Programming & Operation Examples :
1. Set keypad to programming mode with master code and
key. Taking the previous
programmed master code
3 2 8 9
as example here:
2. Program the egress bu�on with 5 seconds delay momentarily mode:
Operation
--- Press the egress bu�on momentary, the keypad will beep for 5 seconds before the
door is open to warn that someone is preparing to exit the protected area.
3. Program the egress bu�on with 5 seconds delay hold contact mode:
Operation
--- Press and hold the egress bu�on for 5 seconds. The keypad will beep for those 5
seconds before the door is Open to warn that someone is preparing to exit the
protected area .
4. Program the egress bu�on to return to default se�ng:
Operation
--- Press the egress bu�on momentarily, the door is open instantly without warning.
5. Exit programming mode by pressing the
Egress Delay & Warning
(Location 85)
11
22