Figure 32. HR/Aux COND flow switch wiring, ref. 50712747
RE
D
1A29 DUAL HIGH VOLTAGE BINARY INPUT
4
4
1
2
1
J2
RED
J11
J1
1
1
J3
2
WATER FLOW SWITCH
AUX CONDENSER
HEAT RECOVERY
1X2-G
OPTIONAL
2K
14B
1X1-3
1X2-10
d
P
5S11
5K3
REQUIRED
OPTIONAL
AUX CONDENSER
WATER FLOW SWITCH
HEAT RECOVERY
1X1-21
Installation
28
CVRF-SVN005C-EN
Energy Meter Option Installation
The Trane energy meter provides instrument grade accuracy
power, volts and amps monitoring of Symbio™ controls
installations. It has 1% accuracy for measuring both real power
and energy and reactive power and energy. All data measured
by the meter is communicated via Modbus to Symbio™ control
system. See BAS-SVN224*-EN for more information.
Figure 33. Energy meter
The meter is connected to line voltage of up to 480 volts and
should be mounted within the starter cabinet. It is provided with
a mounting bracket that can either be mounted on DIN rail or
directly to the starter cabinet wall using the provided bracket.
Figure 34. Mounting bracket