background image

Installation

CVRF-SVN005C-EN

17 

Oil Pressure Transducer Installation

WARNING

Hazardous Voltage w/Capacitors!

Failure to disconnect power and discharge capacitors 

before servicing could result in death or serious injury. 

Disconnect all electric power, including remote 

disconnects and discharge all motor start/run 

capacitors before servicing. Follow proper lockout/

tagout procedures to ensure the power cannot be 

inadvertently energized. For variable frequency drives 

or other energy storing components provided by Trane 

or others, refer to the appropriate manufacturer’s 

literature for allowable waiting periods for discharge of 

capacitors. Verify with a CAT III or IV voltmeter rated per 

NFPA 70E that all capacitors have discharged.

WARNING

PPE for Arc/Flash Required!

Failure to wear appropriate PPE could result in death or 

serious injury. 

On this unit, if the handle shield is cracked the circuit 

breaker could arc/flash when reset. To avoid being 

injured, technicians MUST put on all necessary 

Personal Protective Equipment (PPE), in accordance 

with NFPA70E for arc/flash protection, PRIOR to 

entering the starter panel cabinet.

The two existing oil pressure transducers will be replaced with 
new transducers.
1. Use Loctite 565 on pressure transducer so connection can 

be broken without heat if future replacement of pressure 
transducer is required. Note which line is oil pump 
discharge pressure and which is sump pressure. Quickly 
attach sensors to lines to avoid large quantities of air 
entering machine.
Adapter fittings are provided with the kit. The transducers 
can be mounted in any direction. Lines should be routed 
and transducers mounted to minimize any potential 
stacking of liquid on top of the transducers.

2. Label pressure transducers using labels provided.

Sensor Installation and Wiring

Existing UCP2 sensors cannot be used with a Symbio™ 
retrofit. It is recommended that existing bulb wells be used. 
Installing new wells would necessitate opening the chiller to 
atmosphere

WARNING

Refrigerant under High Pressure!

Failure to follow instructions below could result in an 

explosion which could result in death or serious injury 

or equipment damage. 

System contains refrigerant under high pressure. 

Recover refrigerant to relieve pressure before opening 

the system. See unit nameplate for refrigerant type. Do 

not use non-approved refrigerants, refrigerant 

substitutes, or refrigerant additives.

If installing new bulb wells (optional), use safe refrigerant 
practices to evacuate the chiller. Install and wire each of the 
temperature sensors listed below.
When the sensor is installed in a bulb well, be sure to:

Add thermastic paste to each bulb well before inserting the 
sensor.

Ensure that the sensor “bottoms out” at the base of the bulb 
well.

It is recommended that sensors “1” through “3” be mounted in 
wells. The rest may be installed externally. Connect all 
Symbio™ temperature sensors to the main IPC bus using the 
provided pluggable cables.

NOTICE

Equipment Damage!

Failure to follow instruction below could result in 

equipment damage. Never route low-voltage leads with 

other conductors carrying 30 or more volts.

The Symbio™ component identification is in parenthesis 
following each sensor name:
1. Oil tank temperature sensor (4R5)
2. Evaporator leaving water temperature sensor (4R7)
3. Evaporator saturated refrigerant temperature sensor 

(4R10)

4. Condenser entering and leaving water temperature 

sensors (4R8 and 4R9)

5. Evaporator entering water temperature sensor (4R6)
6. Condenser saturated refrigerant temperature sensor 

(4R11)
Locate sensor at the bottom of the condenser or on the 
condenser liquid line upstream of any orifices or float 
valves.

Note:

If unit has an EarthWise™ purge, PRGD (CH530 
controls), the sensor bound as Condenser Saturated 
Refrigerant Temperature Sensor (used as Purge 
Liquid Temperature) cannot be used and will need to 
be unbound. Install the temperature sensor sent with 
the Tracer® AdaptiView™ components as described 
above.

Summary of Contents for Symbio CVRF

Page 1: ...apart from the Symbio control panel SAFETY WARNING Only qualified personnel should install and service the equipment The installation starting up and servicing of heating ventilating and air condition...

Page 2: ...that is used in these service procedures In addition some states or municipalities may have additional requirements that must also be adhered to for responsible management of refrigerants Know the ap...

Page 3: ...his document and the information in it are the property of Trane and may not be used or reproduced in whole or in part without written permission Trane reserves the right to revise this publication at...

Page 4: ...Purge 21 PRGD PRGG and PRGF EarthWise Purge 21 LONTALK Option Installation 22 Communication Option Installation 22 Wi Fi Installation 22 Air Fi Installation 23 LTE Modem Installation 23 Communication...

Page 5: ...s before you attempt to perform the control system conversion Application Guidelines This Symbio control package is specifically designed to upgrade the controls of CVHE CVHF and CHVG water cooled chi...

Page 6: ...or chillers KIT18458 KIT ECHELON MODULE FIELD INSTALL KIT DAIO Dual analog input and output BRD04875 DBI Dual low voltage binary input BRD04873 DHVBI Dual high voltage binary input BRD04874 DRO Dual r...

Page 7: ...LID Name Description Part Number Table 4 Field installed LLIDs for various options DBI DHVBI DBO HPRO QRO DAIO LON IGV PS 475 PSI Temp Sensor PS 0 to 50 or 475 PSI Starter Module Color Display WiFi Ai...

Page 8: ...eplacement This is a partial list in addition to normal service tools and hardware Type A to Type B USB cable Computer having Tracer TU version 13 0 or newer Digital multi meter with phase detection c...

Page 9: ...ssure transducers on the copper oil lines Table 5 Fusing added for 2F1 2F2 and 2F3 as needed for optional PT transformers Voltage Vac Fuse A Voltage Vac Fuse A 200 1 600 1 230 1 2400 1 380 1 4200 1 46...

Page 10: ...None A 480 Vac or less B Greater than 600 Vac C 2300 2400 Vac D 3300 Vac E 4200 Vac F 6600 Vac 50 Hz Digit 10 11 Design Sequence A0 1st Design sequence Digit 12 Actuator 1 Stepper actuator 2 Pulse act...

Page 11: ...B Starter module with plate for low voltage remote starter C Starter module with plate for unit AFD D Starter module with plate for remote AFD E Starter module with plate for medium voltage unit star...

Page 12: ...trol panel disconnect switches and secure them in that position WARNING Hazardous Voltage w Capacitors Failure to disconnect power and discharge capacitors before servicing could result in death or se...

Page 13: ...1 to H2 If you have wired a temporary thermostat and 115 Vac power source to the oil heater leads wait to connect these wires until the Tracer AdaptiView retrofit is complete to avoid too much cooling...

Page 14: ...the control panel select the side that s most suitable for your specific application Note There is a production display arm bracket BRK04345 provided that where applicable can be mounted to the existi...

Page 15: ...es not spring up or sag down out of the position it is moved to by the operator CAUTION Tension in Display Support Arm Failure to follow instructions below could result in unexpected movement of the s...

Page 16: ...s labeled with loosen tighten or indicators Figure 7 Joint locations on the display arm 2 Joint 3 has a 6 mm hex screw controlling the tension on a gas spring which allows the Tracer AdaptiView displa...

Page 17: ...commended that existing bulb wells be used Installing new wells would necessitate opening the chiller to atmosphere WARNING Refrigerant under High Pressure Failure to follow instructions below could r...

Page 18: ...the hole in the strain relief Figure 10 Strain relief Option I O Installation Wire additional LLIDs as shown on schematics Pay careful attention to which LLIDs require low voltage inputs and which ar...

Page 19: ...bus on the chiller The Symbio retrofit kit includes a general wire kit that has several different types of wires An example of a wiring layout can be seen in Figure 12 p 20 Each application will vary...

Page 20: ...the correct cables so that you don t have any open plugs when finished Avoid placing wire ties directly over plug connectors This may press on the locking mechanism and over time the plugs may release...

Page 21: ...LID 3A6 will not be needed disconnect and remove 2 The condenser saturated refrigerant temperature LLID purge liquid temperature will not be needed disconnect and remove 3 The existing 120 27 Vac tran...

Page 22: ...N005C EN LONTALK Option Installation Symbio 800 system uses a U60 LON module through the USB connection instead of the LCI C LLID 1 Install the U60 LON module KIT18458 KIT ECHELON MODULE FIELD INSTALL...

Page 23: ...e 20 Air Fi wiring ref 50712738 LTE Modem Installation Modem part is MOD03184 MODULE CELLULARLE USB 2 9 METER CABLE Refer to provided literature for setup and operation details 1 Drill a 1 36 inch hol...

Page 24: ...tallation standard application need to field drill a 1 09 inch hole on side of box for a snap bushing This bush can be replaced as field straight connector and conduit 3 4 inch size as NEMA 4 applicat...

Page 25: ...re two transducer 0185 3475 0100 provided per heat exchanger Field connect by male to 2 female 1000mm branch cable CAB01147 which provided in package Figure 26 Standard accuracy option Mounting of Flo...

Page 26: ...ovided Meter Option The high accuracy customer provided meter option provides an analog input output LLID to monitor a customer provided high accuracy meter 0 10 Vdc or 4 20 mA outputs Rosemont etc Th...

Page 27: ...following Wire AWG From To 14B 16 1A29 J3 2 1X1 21 2K 16 1A29 J3 1 1X2 10 4 4 RED J11 1 J1 1 OPTIONALWA TER FLOW METE R CUSTOMER PROVIDE 4 20MA INPUT 1A21 DUAL ANALOG I O OPTIONA L INPUT 1 OUTPUT1 2...

Page 28: ...ent grade accuracy power volts and amps monitoring of Symbio controls installations It has 1 accuracy for measuring both real power and energy and reactive power and energy All data measured by the me...

Page 29: ...minated at the Modbus distribution terminal 1X3 beside Symbio 800 using the 3 poles connector which provide in energy meter kits Figure 36 Distribution terminal Figure 37 Modbus wiring ref 50712738 48...

Page 30: ...0 2T51 2T52 LINE 99 TO 1X3 WHT BLK WHT BLK WHT BLK RED BLK BLU YEL ORG BRN WHT 2F54 2F52 2F53 0 5A 0 5A 0 5A DETAIL A ENERGY METER OPTION NOT USED WB22 X1 X2 X1 X2 X1 X2 G MODBUS VOLTINPUTS L1 L2 L3 N...

Page 31: ...e start relay start capacitor and related wiring from Symbio panel and discard These items will not be used in this application 2 Wire oil pump contactor coil between terminals 1X1 14 and 1X1 6 as per...

Page 32: ...and 1X1 6 per schematic Figure 43 Refrigerant oil pump wiring ref 50712738 Installation of Oil Pump Motor Wiring and Terminals The CVRF installation will relocate the oil pump relay to the control pa...

Page 33: ...of the dry run test can be performed The pilot relay method must be used when the contactor coils are voltages other than 115 Vac If both direct control or pilot relay control can be used on your app...

Page 34: ...needed A description of the sub panel s types and uses is below Table 8 Sub panel types Model Digit 33 Application Part Number Description Starter Mount Type PTs Configuration Selection FACT FCOD E St...

Page 35: ...e and black leads on the sub panel in the order below Note If replacing a UCP2 starter module you can remove and discard the 27 VAC UCP2 starter module transformer as it is not required for the CH530...

Page 36: ...Figure 49 Pilot relay switching configuration Figure 50 Wye delta interlock and pilot relay wiring Starter Work 36 CVRF SVN005C EN...

Page 37: ...as follows 1 Remove existing UCP2 module keeping potential transformers and secondary current transformers if needed for reuse 2 Install existing potential transformers on lower panel if required and...

Page 38: ...to refer to the wiring diagrams listed in Wiring Diagram Matrix p 46 as you review the following instructions The wire numbers and component designations indicated in these steps appear in these figu...

Page 39: ...ications to starter module b For remote mount AFDs i Wire per schematic starter module will be powered by sub panel power supply ii Use existing communications cable to connect Symbio communications b...

Page 40: ...and its orientation The polarity dot should face incoming power in other words towards the disconnect Figure 55 Current transformer single turn down Wire the leads from the CT male quick connects to t...

Page 41: ...ordered secondary CTs In this case two CTs are used per phase to either achieve the necessary turn down or for metering convenience The first stage consists of either the X13580271010 TRR01287 X135802...

Page 42: ...600 05 00 600 2 5 1 432 336 504 TRR00451 TRR00975 700 05 00 700 2 5 1 504 384 576 TRR00451 TRR00975 800 05 00 800 2 5 1 576 480 720 TRR00451 TRR00975 1000 05 00 1000 2 5 1 720 480 720 TRR00655 TRR0097...

Page 43: ...Figure 57 Dual CT wiring example Starter Work CVRF SVN005C EN 43...

Page 44: ...ater than 600 Vac a large medium voltage PT is used to step from line voltage to 115 Vac and a second PT steps the voltage to less than 30 Vac The large PT is a three phase type except for the 6600 Va...

Page 45: ...ering the starter panel cabinet NOTICE Module Damage Failure to follow the following instruction could result in equipment damage Do NOT connect the secondaries of the line to 120 Vac potential transf...

Page 46: ...50710524 Primary Reactor CS 50710525 Auto X Former CS 50710527 Starter Subpanel VFD 50711536 Energy Meter Option 480V and Low 50712756 Energy Meter Option 575 and 600V 50712757 Energy Meter Option MV...

Page 47: ...Notes CVRF SVN005C EN 47...

Page 48: ...re committed to using environmentally conscious print practices Trane by Trane Technologies NYSE TT a global climate innovator creates comfortable energy efficient indoor environments for commercial a...

Reviews: