Diagnostics
96
RTAF-SVX001K-EN
Comm Loss: Oil Loss Level Sensor Input
Comm Loss: Oil Loss Level Sensor Input
Comm: Oil Level Sensor
Circuit
Normal
Latch
All
Continual loss of communication between
the MP and the Functional ID has occurred
for a 30 second period.
Remote
Comm Loss: Oil Pressure - xy
Comm: Oil Pressure - xy
Cprsr
Immediate
Latch
All
Continual loss of communication between
the MP and the Functional ID has occurred
for a 30 second period.
Remote
Comm Loss: Oil Return Line Solenoid
Valve -xy
Comm Loss: Oil Return Solenoid Valve - xy
Comm: Oil Ret Sol Vlv xy
Cprsr
Normal
Latch
All
Continual loss of communication between
the MP and the Functional ID has occurred
for a 30 second period.
Remote
Comm Loss: Outdoor Air Temperature
Comm: Outdoor Air Temp
Chiller
Normal
Latch
All
Continual loss of communication between
the MP and the Functional ID has occurred
for a 30 second period.
Remote
Comm Loss: Programmable Relay Board 1
Comm: Program Relay Board 1
None
Info
Latch
All
Continual loss of communication between
the MP and the Functional ID has occurred
for a 30 second period.
Remote
Comm Loss: Programmable Relay Board 2
Comm: Program Relay Board 2
None
Info
Latch
All
Continual loss of communication between
the MP and the Functional ID has occurred
for a 30 second period.
Remote
Comm Loss: Slide Valve Load - xy
Comm: Slide Valve Load - xy
Cprsr
Normal
Latch
All
Continual loss of communication between
the MP and the Functional ID has occurred
for a 30 second period.
Remote
Comm Loss: Slide Valve Unload - xy
Comm: Slide Valve Unload - xy
Cprsr
Normal
Latch
All
Continual loss of communication between
the MP and the Functional ID has occurred
for a 30 second period.
Remote
Comm Loss: Starter xy
Cprsr
Immediate
Latch
All
Continual loss of communication between
the MP and the Functional ID has occurred
for a 30 second period.
Local
Comm Loss: Step Load - xy
Comm: Step Load - xy
Cprsr
Normal
Latch
All
Continual loss of communication between
the MP and the Functional ID has occurred
for a 30 second period.
Remote
Comm Loss: Suction Refrigerant
Pressure - xy
Comm Loss: Suction Rfgt Pressure - xy
Comm: Suction Rfgt Press xy
Cprsr
Immediate
Latch
All [Ckt/
Cprsr lock
out]
Continual loss of communication between
the MP and the Functional ID has occurred
for a 30 second period.
Remote
Comm Loss: Water System Differential
Pressure
Comm Loss: Water System Diff Pressure
Comm: Water Sys Diff Press
Chiller
Info
Latch
All
Continual loss of communication between
the MP and the Functional ID has occurred
for a 30 second period.
Remote
Table 34. Communications diagnostics (continued)
Diagnostic Name
Affects
Target
Severity Persistence
Active
Modes
[Inactive
Modes]
Criteria
Reset
Level