Diagnostics
RTAF-SVX001K-EN
91
Very Low Evaporator Rfgt Pressure - xy
Very Low Evap Rfgt Pressure - xy
Very Low Evap Rfgt Press xy
Chiller Immediate
Latch
All
The respective circuit’s evaporator
pressure dropped below 80% of the
current Low Evap Refrig Press Cutout
setting (see above) or 8 psia, whichever is
less, regardless of the running state of the
circuit’s compressor. Note: Unlike previous
products, even if the circuit associated
with the suction pressure sensor is locked
out, it will not defeat the protection
afforded by this diagnostic.
Local
Water System Differential Pressure
Water System Diff Pressure
Chiller
Info
Latch
All
Bad Sensor or LLID
Remote
Table 33. Main processor diagnostics (continued)
Diagnostic Name
Affects
Target
Severity Persistence
Active
Modes
[Inactive
Modes]
Criteria
Reset
Level