Diagnostics
86
RTAF-SVX001K-EN
High Evaporator Shell Refrigerant
Pressure – Circuit 1
High Evap Shell Rfgt Pressure - Ckt1
High Evap Shell Press Ckt1
Chiller Immediate
NonLatch
All
The evaporator shell refrigerant pressure
is installed, is valid, and has risen above
190 psig.
- De-energize evaporator water pump
regardless of why the pump is running.
- Open the circuit’s EXV to 20% to allow
refrigerant flow to other parts of the chiller,
if liquid line refrigerant pressure is less
than 170 psig. Return EXV to normal
control (allow it to close until needed for
circuit operation) if liquid line refrigerant
pressure is greater than 175 psig.
Automatically clear diagnostic when
evaporator shell refrigerant pressure is
valid and drops below 180 psig.
- Allow evaporator water pump to return to
normal control.
- Return circuit’s EXV to normal control
(allow it to close until needed for circuit
operation).
Primary causes of this diagnostic:
- Evaporator water pump heat transferred
to evaporator, either by flow blockage, or
by lack of heat dissipation in the water loop
in the presence of flow.
- Commissioning unit in high ambient
temperature environments.
- Water box heater thermostat failed
closed.
Remote
High Evaporator Shell Refrigerant
Pressure – Circuit 2
High Evap Shell Rfgt Pressure - Ckt2
High Evap Shell Press Ckt2
Chiller Immediate
NonLatch
All
See Circuit 1 description.
Remote
High Evaporator Water Temperature
High Evap Water Temperature
Chiller
Info and
Special
Action
NonLatch
Only effective if
either
1)Evap Wtr
Flow Overdue
2)Evap Wtr
Flow Loss or
3)Low Evap
Rfgt Temp,-
Unit Off,
diagnostic is
active.
Either the leaving or the entering water
temperature exceeded the high evap
water temp limit (TU service menu
settable –default 105F(65.55C), range
80F(26.67C)-150F(65.55C) for 15
continuous seconds. The evaporator water
pump relay will be de-energized to stop
the pump but only if it is running due one
of the diagnostics listed on the left. The
diagnostic will auto reset and the pump will
return to normal control when both the
entering and leaving temperatures fall 5°F
below the trip setting. The primary
purpose is to stop the evaporator water
pump and its associated pump heat from
causing excessive waterside temperatures
and waterside pressures when the chiller is
not running but the evap pump is on due
to either Evap Water Flow Overdue,
Evaporator Water Flow Loss, or Low Evap
Temp – Unit Off Diagnostics. This
diagnostic will not auto clear solely due to
the clearing of the enabling diagnostic.
Remote
High Motor Winding Temperature – xA
High Mtr Windng Temp - xA
Circuit Immediate
Latch
All
The respective compressor’s motor
winding thermostat is detected to be open.
The compressor shall stop within 5
seconds of this diagnostic.
Local
High Oil Temperature - xy
Cprsr
Immediate
Latch
All
[compressor
run unload or
compressor not
running]
The oil temperature entering the
compressor exceeded 199.4°F.
Remote
Table 33. Main processor diagnostics (continued)
Diagnostic Name
Affects
Target
Severity Persistence
Active
Modes
[Inactive
Modes]
Criteria
Reset
Level