38
RT-SVX063G-EN
Supply Fans
Remove Shipping Tie Down
Remove supply fan shipping tie down hardware. There are
four places on each fan where hardware needs to be
removed, shown in
. Gently spin each fan
to verify there is no wheel-to-cone interference. If
adjustment is required, loosen fan shaft set screw and
reposition fan to get correct wheel/cone overlap.
Figure 17.
Remove shipping tie-downs
Tiedown
Tiedown
Clearance
Clearance
Figure 18.
Shipping tie-down
Important:
Do NOT remove electrical ground wire strap.
Table 11.
Supply fan cone overlap measurements
Fan Size
Cone Width G (in.)
Overlap Q (in.)
165
5.18
0.18
182
6.44
0.38
200
7.05
0.41
Table 11.
Supply fan cone overlap measurements
(continued)
Fan Size
Cone Width G (in.)
Overlap Q (in.)
222
7.83
0.45
245
8.62
0.50
270
9.45
0.55
Summary of Contents for IntelliPak with Symbio 800