52
RT-SVX063G-EN
Table 19.
Outside air damper pressure drop — Traq™
Traq™
CFM
Outside Air Damper Position
#1
#2
#3
#4
#5
#6
20, 25 and 30 Ton
4000
0.07
0.08
0.09
0.17
0.26
0.89
6000
0.15
0.18
0.21
0.40
0.64
2.82
7000
0.20
0.26
0.31
0.56
0.90
-
8000
0.26
0.35
0.43
0.73
1.19
-
9000
0.32
0.45
0.56
0.93
1.53
-
10000
0.40
0.57
0.71
1.15
1.91
-
11000
0.47
0.70
0.88
1.40
2.33
-
12000
0.56
0.85
1.06
1.67
2.79
-
13000
0.65
1.01
1.27
1.97
-
-
40, 50 and 55 Ton
8000
0.23
0.40
0.46
0.89
1.75
-
10000
0.35
0.56
0.65
1.33
2.57
-
12000
0.49
0.73
0.86
1.85
-
-
14000
0.66
0.93
1.11
2.45
-
-
16000
0.85
1.15
1.38
-
-
-
18000
1.07
1.39
1.68
-
-
-
20000
1.31
1.64
2.00
-
-
-
22000
1.57
1.92
2.36
-
-
-
24000
1.86
2.23
2.74
-
-
-
Table 20.
Return air pressure increase
CFM
Return Air Damper Position
#1
#2
#3
#4
20, 25 and 30 Ton
4000
0.00
0.01
0.06
0.06
6000
0.00
0.02
0.09
0.14
7000
0.00
0.03
0.11
0.19
8000
0.00
0.03
0.13
0.25
9000
0.00
0.04
0.14
0.31
10000
0.00
0.04
0.16
0.38
11000
0.00
0.05
0.18
0.46
12000
0.00
0.05
0.20
0.55
13000
0.00
0.06
0.22
0.65
40, 50 and 55 Ton
8000
0.00
0.07
0.15
0.17
10000
0.00
0.09
0.19
0.24
12000
0.00
0.10
0.22
0.33
Summary of Contents for IntelliPak with Symbio 800
Page 64: ...64 RT SVX063G EN Figure 37 Dry bulb changeover map Startup the Unit ...
Page 137: ...RT SVX063G EN 137 Notes ...
Page 138: ...138 RT SVX063G EN Notes ...
Page 139: ...RT SVX063G EN 139 Notes ...