RT-SVX063G-EN
37
Figure 16.
Typical field power wiring (20 to 75 ton)
3-WIRE POWER SUPPLY
PLUS GROUND
3-WIRE POWER SUPPLY
PLUS GROUND
PITCH
POCKET
PITCH
FIELD SUPPLIED DISCONNECT SWITCH
RE 200/230 ONLY: ADDITIONAL FIELD SUPPLIED DISCONNECT SWITCH
Table 10.
Customer connection wire range
Units with Main Power Terminal Block (All Voltages)
Units with Main Power Disconnect Switch (All Voltages)
Block Size
Wire Qty
Connector Wire
Range
Block Size
Wire Qty
Connector Wire
Range
510 AMP
2
#6 — 250 kcmil
250 AMP
1
3/0 - 350 kcmil
760 AMP
2
#4 — 500 MCM
400 AMP
2
2/0 - 500 kcmil
600 AMP
2
2/0 - 500 kcmil
Note:
Block size and disconnect size are calculated by selecting the size greater than or equal to 1.15 x (Sum of Unit Loads). See unit literature for unit load values.
250A Disconnect switch wire binding screws
The 250A disconnect switch (standard and high SCCR)
installed for main power connection accommodates 4 AWG
– 350 kcmil wires on the "OFF" side. As shipped from the
factory, the wire binding screws only accommodate 3/0
AWG – 350 kcmil wires. If 4 AWG – 2/0 AWG field power
wiring is used, then the factory installed wire binding
screws must be replaced with those that are provided with
the kit installed near the disconnect switch (these screws
should have a blue top surface). See the kit for instructions
on changing the wire binding screws.