Job Name:
Location:
Date:
Purchaser: Engineer:
Submitted to:
For Reference Approval Construction
System Designation:
Schedule No.:
Cooling Capacity*
. . . . . . . . . . . . . . . . . . . . . . . . . . . .11,100 Btu/h
Heating Capacity*
. . . . . . . . . . . . . . . . . . . . . . . . . . . .13,600 Btu/h
*
Rating Conditions (Cooling) - Indoor: 80ºF (27ºC) DB, 67ºF (19ºC) WB; Outdoor: 95ºF
(35ºC) DB, 75ºF (24ºC) WB.
(Heating at 47ºF) - Indoor: 70ºF (21ºC) DB, 60ºF (16ºC) WB; Outdoor: 47ºF (8ºC) DB, 43ºF (6ºC) WB.
(For data on specific indoor units combinations [all ducted, all non-ducted, and both
ducted and non-ducted], see the MXZ-B Technical and Service Manual.)
Electrical Requirements
Power Supply . . . . . . . . . . . . . . . . . . . . 208 / 230V, 1-Phase, 60 Hz
MCA . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 A
Voltage
Indoor - Outdoor S1-S2 . . . . . . . . . . . . . . . . . . . . . . AC 208 / 230V
Indoor - Outdoor S2-S3 . . . . . . . . . . . . . . . . . . . . . . . . . DC 12-24V
Fan Motor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 0.28 F.L.A.
Airflow (Lo - Med - Hi)
. . . . . . . . . . . . . . . . . 280 - 320 - 390 Dry CFM
250 - 290 - 350 Wet CFM
Air Filter . . . . . . . . . . . . . . . . . . . . . . . . .Polypropylene Honeycomb
Sound Pressure Level (Lo - Med - Hi) . . . . . . . . .30 - 34 - 39 dB(A)
DIMENSIONS
UNIT INCHES / MM GRILLE INCHES / MM
W
22-7/16 / 570
25-5/8 / 650
D
22-7/16 / 570
25-5/8 / 650
H
8-3/16 / 208
13/16 / 19
Weight (Unit/Grille)
Lbs... . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36 / 7
kg. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16 / 3
External Finish (Unit/Grille) . . . . . . . . . . Galvanized-steel Sheets /
Munsell 6.4Y 8.9 / 0.4
Field Drainpipe Size O.D.. . . . . . . . . . . . . . . . . . . . . 1-1/4” / 32 mm
Refrigerant Type. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .R410A
Refrigerant Pipe Size O.D.
Gas Side . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3/8" / 9.52 mm
Liquid Side. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1/4" / 6.35 mm
Connection Method . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Flared
SUBMITTAL DATA: SLZ-KA12NA
. . . . . . . . 12,000 BTU/H CEILING-CASSETTE INDOOR UNIT FOR MXZ-B MULTI-ZONE HEAT-PUMP SYSTEMS
MXZ-B SERIES HEAT-PUMP OUTDOOR UNITS
SEZ-KD and PEAD-A24
MSZ-GE
MXZ-B MULTI-ZONE SYSTEMS CAN INCLUDE:
• Ducted Indoor Units:
SEZ-KD09,12,15,18NA, PEAD-A24AA
• Nonducted Indoor Units:
MSZ-GE06,09,12,15,18,24NA,
MSZ-FE09,12,18NA, MFZ-KA09,12,18NA,
PCA-A24KA, SLZ-KA09,12,15NA, and
PLA-A12,18,24BA
• A combination of both Ducted and Nonducted
Indoor Units
Refer to the separate submittal forms for the
MSZ-GE, MSZ-FE, SEZ-KD, SLZ-KA, PEAD,
PCA, PLA Indoor Units, and MXZ Outdoor Units.
Outdoor Unit: MXZ-3B30NA
MSZ-FE
MFZ-KA
PCA-KA
SLZ-KA and PLA-ABA
OPTIONAL ACCESSORIES
Indoor Unit
□
Grille (SLP-15AAUW; required - shipped with unit)
GENERAL FEATURES
• Four-way 2'x2' ceiling-cassette indoor unit for residential
applications
• Built-in drain mechanism for condensate removal; lifts to
19-11/16
"
• Wide air-flow pattern for better air distribution
• Design features ventilation air intake knockout
• Long-life air filter included with indoor unit
• Indoor unit powered from outdoor unit using A-Control
• Automatic fan speed control; auto restart following a power outage
• Limited warranty: five years on parts/defects, seven years on
compressors
Controller Options
□
Wall-mounted Wired Remote Controller (PAR-21MAA)
□
M-NET Control Adapter (MAC-399IF)
□
Remote Temperature Sensor (M21-JKO-307)
□
Handheld Wireless Remote Controller (PAR-FL32MA;
req. PAR-SA9FA)
□
Receiver Kit for PAR-FL32MA Handheld Wireless Remote
Controller (PAR-SA9FA)
□
Lockdown Bracket for Handheld Controller (RCMKP1CB)
SLZ-KA12NA