SETPOINT Menu
38
PKG-SVP01E-EN
Low Ambient Comp Lockout Temp:
50 F
Used With: All Units
Factory Presets: 50 F
Possible Values: -20 F to 80 F
Comp(s) OFF if OA Temp Below This Value
1.
Press the NEXT key until the following screen is displayed.
Setpoint Source Selections Submenu
Used With: All Units
Press ENTER to Review or Adjust
1.
Press the NEXT key until the following screen is displayed.
For Supply Air Temp Cooling Control,
Use
Used With: All Units
Factory Presets: HI (Keypad) Setpoint Menu
Possible Values: HI (KEYPAD) SETPOINT
MENU, ZONE SENSOR SETPOINT MENU, NSB
PANEL SETPOINT INPUT, GBAS 0-5 VDC
MODULE
Setpoint From: HI (KEYPAD) SETPOINT MENU
1.
Press the NEXT key until the following screen is displayed.
For Supply Air Temp Heating Control,
Use
Used With: All Units when hydronic or electric
heat is installed.
Factory Presets: HI (Keypad) Setpoint Menu
Possible Values: HI (KEYPAD) SETPOINT
MENU, GBAS 0-5VDC Module
SETPOINT From: HI (KEYPAD) SETPOINT MENU
1.
Press the NEXT key until the following screen is displayed.
For Occ Zone Temp Cooling Control, Use
Used With: All Units
Factory Presets: HI (KEYPAD) SETPOINT
MENU
Possible Values: HI (KEYPAD) SETPOINT
MENU, ZONE SENSOR SETPOINT INPUT, NSB
PANEL SETPOINT INPUT, GBAS 0-5 VDC
MODULE
SETPOINT From: HI (KEYPAD) SETPOINT MENU
1.
Press the NEXT key until the following screen is displayed.
For Occ Zone Temp Heating Control, Use
Used With: All Units with hydronic or electric
heat.
Factory Presets: HI (KEYPAD) SETPOINT
MENU
Possible Values: HI (KEYPAD) SETPOINT
MENU, ZONE SENSOR SETPOINT INPUT, NSB
PANEL SETPOINT INPUT, GBAS 0-5 VDC
MODULE
SETPOINT From: HI (KEYPAD) SETPOINT MENU
1.
Press the NEXT key until the following screen is displayed.
For Unocc Zone Temp Cooling Control, Use
Used With: All Units
Factory Presets: HI (KEYPAD) SETPOINT
MENU
Possible Values: HI (KEYPAD) SETPOINT
MENU, ZONE SENSOR SETPOINT INPUT, NSB
PANEL SETPOINT INPUT, GBAS 0-5 VDC
MODULE
Setpoint From: HI (KEYPAD) SETPOINT MENU
1.
Press the NEXT key until the following screen is displayed.
For Unocc Zone Temp Heating Control, Use
Used With: All Units when External, Electric or
Hydronic Heat is installed
Factory Presets: HI (KEYPAD) SETPOINT
MENU
Possible Values: HI (KEYPAD) SETPOINT
MENU, ZONE SENSOR SETPOINT INPUT, NSB
PANEL SETPOINT INPUT, GBAS 0-5 VDC
MODULE, GBAS 0-10VDC Module
Setpoint From: HI (KEYPAD) SETPOINT MENU
1.
Press the NEXT key until the following screen is displayed.
For Morning Warmup Temp Control, Use
Used With: All Units when Electric, External or
Hydronic Heat is installed
Factory Presets: HI (KEYPAD) SETPOINT
MENU
Possible Values: HI (KEYPAD) SETPOINT
MENU, NSB PANEL SETPOINT INPUT
GBAS 0-5VDC Module
Setpoint From: HI (KEYPAD) SETPOINT MENU
1.
Press the NEXT key until the following screen is displayed.