Programming SETUP
26
PKG-SVP01E-EN
Water Economizer Min Position: 10%
Used With: Units with a waterside economizer
Possible Values: 0-100%
1.
Press the NEXT key until the following screen is displayed.
Select Water Flow Control Required For
Used With: Water-cooled units with a
waterside economizer installed.
Possible Values: Constant/Maximize;
Variable/Minimize
Water Pump System: Variable/Minimize
1.
Press the NEXT key until the following screen is displayed.
End of Submenu (NEXT) to Enter SETUP
1.
Press the NEXT key until the following screen is displayed
Head Pressure Ctrl Setup Submenu
Press Enter to Review or Adjust
1.
Press the NEXT key until the following screen is displayed
Used With: All water-cooled units.
Possible Values: 80 - 100 F
Cond Temp Control Point: 90 F
1.
Press the NEXT key until the following screen is displayed
Preset Value to Min if Cond Water Below
Used With: All water-cooled units.
Possible Values: 80 - 100 F
Head Press Value Preset Temp Limit: 90 F
1.
Press the NEXT key until the following screen is displayed
Cond Temp Control Band
Used With: All air-cooled units
Factory Presets: Upper: 120 F, Lower: 80 F
Possible Values: Lower: 70 F to 90 F, Upper:
110 F to 130 F
Lower Limit: 80 F Upper Limit: 120 F
1.
Press the NEXT key until the following screen is displayed.
Cond Temp Control Band
Used With: All air-cooled units
Factory Presets: 10 F
Possible Values: 0 to 20 F
Temporary Low Limit Suppression:
10 F
1.
Press the NEXT key until the following screen is displayed.
Cond Temp
Used With: All air-cooled units
Factory Presets: 105 F
Possible Values: 95 to 115 F
Efficiency Check Point:
105 F
1.
Press the NEXT key until the following screen is displayed.
Cond Temp
Used With: All air-cooled units
Factory Presets: 90 F
Possible Values: 80 F to 100 F
Low Ambient Control Point:
90 F
1.
Press the NEXT key until the following screen is displayed.
End of Submenu (NEXT) to Enter SETUP
1.
Press the NEXT key to leave the submenu and show following screen.
Sensor Source Selections Submenu
Sensor Source Selections Submenu
Used with: All Units.
Press ENTER to Review or Adjust
1.
Pressing the NEXT key will bypass this section.