DIAGNOSTICS Menu

PKG-SVP01E-EN

47

Failure Modes

When any condition results in the rooftop unit’s inability to

perform a normal function, it is said to have entered a
failure mode. There are two types of failure modes.

1. An “Analog input out of range” failure mode.

This failure mode occurs when a sensing device such

as a zone temperature sensor or a humidity sensor
begins to transmit information that is outside its
allowable range.

2. A “Fault recognition by input logic” failure mode.

This failure mode occurs when the UCM receives

information that does not “make sense” or does not
conform to its predefined logic.

Diagnostics Types

There are three types of diagnostics:

1.

Informational - Does not affect machine operation.

2. Automatic Reset - Affects machine operation but

returns to normal when diagnostic condition no longer
exists.

3. Manual Reset - Affects machine operation and must be

reset at the HI or by cycling power to unit for normal
operation to resume.

To troubleshoot diagnostics, reference the Installation,

Operation, and Maintenance Manual SCXF-SVX01*-EN

that ships with the Signature Series units and SCXG-
SVX01*-EN that ships with the Modular Series units.

Log 1                                              ___________________
___________________                

Possible Values:

Log number 1-20

Manual

Viewed or Not Viewed

Auto

Active or History

Info

Or any diagnostic listed under the previous screens associated with the diagnostic type 
including VOM activated mode

1.

Press the CANCEL key to clear the diagnostics and prompt the following screen.

Diagnostic Log is Password Protected

Possible Values: + (Plus), - (Minus)

Please Enter Password:       ___________________          

1.

Press the + (Plus) or - (Minus)keys to enter the password.

2.

Press the ENTER key to confirm. After entering the correct password, the following screen will display.

Active Diagnostics        ___________________          

Possible Values: Manual, Auto, or Info

Please Wait, Updating Diagnostic Log

If the DIAGNOSTIC LOG is empty when the CANCEL key is pressed, the following screen will display.

Active Diagnostics        Info

Possible Values: Manual, Auto, or Info

Diagnostic Buffer Is Already Empty!

Press the AUTO or STOP key to return to the top level status screen.

Summary of Contents for IntelliPak SCRG-020

Page 1: ...on the equipment observe all precautions in the literature and on the tags stickers and labels that are attached to the equipment IntelliPak Commercial Self Contained Signature Series 20 110Ton Modul...

Page 2: ...nitor operating status set specific operating parameters and diagnose system problems Some screens shown in this manual are dependent on unit options and or model configuration Therefore some screens...

Page 3: ...eens 13 Programming Status 14 STATUS Menu 14 Programming SETUP 22 SETUP Menu 22 SETUP Menu Screens 22 Sensor Source Selections Submenu 26 Outside Air Ventilation Setup 27 Ventilation Override Definiti...

Page 4: ...uman Interface HO History Only Diagnostic HVAC heating ventilation and air conditioning ICS Integrated Comfort System IGV inlet guide vanes INFO Information Only Diagnostic I O input output Indep Inde...

Page 5: ...ntrol module VDC volts DC Ventil ventilation VFD variable frequency drive Table 1 Acronyms continued VOM ventilation override module VVDA Variable Speed Fan VAV Discharge Air Temp Control W with w c w...

Page 6: ...VOM can control the unit s air handling functions to perform customerspecified functions such as space pressurization exhaust purge unit off etc Interprocessor Communications Board IPCB Option The IP...

Page 7: ...s below UNIT OFF sequence A When complete system shut down is required the following sequence can be used Supply fan Off Supply fan VFD Off 0 Hz if equipped Inlet guide vanes closed if equipped Outsid...

Page 8: ...play Any steps that do not apply to all unit types are marked accordingly Ignore any steps that do not apply to your unit and or application Continue this process until all applicable screens are prog...

Page 9: ...mode screens showing various unit components which may be turned on or off for the particular test being performed Once the status of these components is designated the LCD will display screens that...

Page 10: ...nu press the CUSTOM key then press the NEXT key until the status screen that you want to remove appears then press the Minus key General Status Display Anytime the rooftop unit is powered up or the ST...

Page 11: ...in this manual Note Record any changes made to the factory preset values in the corresponding space provided Table 3 Factory presents Adjustable Function Factory Preset Changed To Reference Page Cont...

Page 12: ...ation format Text displays Unit displays English English p 22 p 22 Reference Enthalpy 25 btu lb p 37 RTM alarm output assignments any active diagnostic p 30 Sensor source selection for Daytime warmup...

Page 13: ...temperature 0 F p 31 Outdoor air 0 F p 31 Ventilation override definitions N A p 28 Table 3 Factory presents continued Adjustable Function Factory Preset Changed To Reference Page Password Entry Time...

Page 14: ...lay RTM Supply Airflow Proving OFF FLOW Possible Values Fan On Off Airflow Flow No Flow 1 Pressing the NEXT key will scroll forward through the screens 2 Pressing the PREVIOUS key will scroll backward...

Page 15: ...nsor low ambient lockout demand limit ventilation override low ent cond water temp 1 Pressing the NEXT key will scroll forward through the screens Compressor Relay K12 Enabled OFF Used With Units with...

Page 16: ...il the following screen is displayed Water Economizing DISABLED Used With Units with a waterside economizer only Possible Values Economizer Disable enable Water econ position opening to closing to 0 1...

Page 17: ...Menu Zone Sensor Setpoint Input NSB Zone Sensor Setpoint Input GBAS 0 5 VDC Module ICS Tracer Summit RTM ZONE TEMP INPUT is 74 F 1 Pressing the NEXT key will scroll forward through the screens Active...

Page 18: ...Possible Values RTM Zone Temp Input NSB Zone Sensor Setpoint Input RTM Aux Temp Input ECEM return Air Temp Input ICS Tracer Summit Sensor Range 40 to 200 F 1 Pressing the NEXT key will scroll forward...

Page 19: ...ollowing screen is displayed if applicable Temperature Input Status Submenu Press ENTER to View Data in This Submenu 1 Pressing the NEXT key will scroll forward through the screens Temp Meausured By S...

Page 20: ...72 0 Sat Cond Temp 87 0 F 1 Pressing the NEXT key will scroll forward through the screens Compressor Module Ckt 3 Used With SCWF SIWF 42 80 tons or SCRF SIRF 50 60 tons only Evap Temp 72 0 Sat Cond Te...

Page 21: ...End of Submenu NEXT to Enter SETUP 1 Press the NEXT key until the following screen is displayed GBAS 0 5VDC Module Staus Submenu Press ENTER to View Data in This Submenu Used With Units with GBAS modu...

Page 22: ...Press the SETUP key to begin viewing or modifying the SETUP screens If a screen is not visible on the Unit Human Interface Module refer to the UsedWith information listed to the right of each screen...

Page 23: ...OINT Used With Units with VCM installed Factory Preset Control Disabled Possible Values Control Enabled Disabled 1 Press the NEXT key until the following screen is displayed Demand Limit Definition Co...

Page 24: ...es SAT Zone OA Reset Zone 72 Reset OA 72 Maximum Amount of Reset Applied 5 F 1 Press the NEXT key until the following screen is displayed Supply Air Temp Outside Air Reset For Heating Used With All Un...

Page 25: ...until the following screen is displayed End of Submenu NEXT to Enter SETUP 1 Press the NEXT key to leave the submenu and show following screen 2 Press PREVIOUS to page back through the submenu Water F...

Page 26: ...mit 90 F 1 Press the NEXT key until the following screen is displayed Cond Temp Control Band Used With All air cooled units Factory Presets Upper 120 F Lower 80 F Possible Values Lower 70 F to 90 F Up...

Page 27: ...INPUT NSB PANEL TEMP SENSOR INPUT RTM AUX TEMP INPUT HEAT MODULE AUX TEMP INPUT ECEM RETURN AIR TEMP INPUT Connected To RTM ZONE TEMP INPUT 1 Press the NEXT key until the following screen is displaye...

Page 28: ...set 250 to 250 CCFM Default 0 CFM Gain 1 0 Offset 0 0 CCFM 1 Press the NEXT key until the following screen is displayed End of Submenu NEXT to Enter SETUP 1 Press the NEXT key to leave the submenu and...

Page 29: ...ble Values ON OFF Supply Fan 1 Follow the preceding steps used to program MODE A to program MODE B C D and E if modifications are needed After all of the Ventilation Override Definitions have been pro...

Page 30: ...er 1 assignment Plus key will assign ALL Diagnostics and Minus key will allow diagnostic selection 3 Press the ENTER key to confirm this choice If Yes was assigned to the Output assignment the output...

Page 31: ...key until the following screen is displayed Temperature Calibration Offset For Used With All Units when Electric or Hydronic Heat is installed Factory Presets 0 0 F Possible Values Plus or Minus 5 0 F...

Page 32: ...installed Factory Presets 0 0 F Possible Values 0 0 5 0 F Ckt 3 Sat Cond Temp Input 0 0 F 1 Press the NEXT key until the following screen is displayed Temperature Calibration Offset For Used With Wate...

Page 33: ...sible Values 0 10 VDC Min Voltage 2 0 VDC 1 Press the NEXT key until the following screen is displayed Actuator Setup Water Econ Bypass Used With All Units when a waterside economizer is installed Fac...

Page 34: ...Voltage 2 0 VDC 1 Press the NEXT key until the following screen is displayed Actuator Setup Num 1 Low Ambient Used With Air cooled units low ambient damper installed Factory Presets 10 0 VDC Possible...

Page 35: ...lgorithmTuning Parameters Applicable to all units Control Algorithm Tuning Parameters Press ENTER to Review or Adjust Note Contact theTrane Company before making any adjustment to these settings 1 Pre...

Page 36: ...to scroll through the SETPOINT submenu choices or d if you want to exit to another menu such as CONFIGURATION press that key once then press the NEXT key toscroll through those screens Default Supply...

Page 37: ...r without an airside economizer with IGV or VFD and a VCM Factory Presets 15 Possible Values 0 100 With IGV VFD Command At Minimum 0 1 Press the NEXT key until the following screen is displayed Defaul...

Page 38: ...NT MENU 1 Press the NEXT key until the following screen is displayed For Occ Zone Temp Heating Control Use Used With All Units with hydronic or electric heat Factory Presets HI KEYPAD SETPOINT MENU Po...

Page 39: ...stalled Factory Presets HI KEYPAD SETPOINT MENU Possible Values HI KEYPAD SETPOINT MENU GBAS 0 5VDC Module Setpoint From HI KEYPAD SETPOINT MENU 1 Press the NEXT key until the following screen is disp...

Page 40: ...press the STATUS key once or b if you want to remain in the Setpoint submenu press the CONFIGURATION key once and it will return you to the beginning of that particular submenu or c if you want to exi...

Page 41: ...uration Model Num Digit 9 Air Temp Vol Ctrl SA CTRL WITH IGV VFD Used With All Units Possible Values SA Control with IGV VFD Zone Control No IGV VFD or SA Control No IGV VFD 1 Press the NEXT key until...

Page 42: ...s with VOM module installed 1 Pressing the NEXT key will scroll forward through the screens Software Revision Number Report Exhaust Comp Enthalpy Module 8 04 Used With Units with Comparative Enthalpy...

Page 43: ...e and it will return you to the beginning of that particular submenu or c if you want to exit to another submenu in the in the SERVICE MODE menu press the CONFIGURATION key twice Then press the NEXT k...

Page 44: ...key until the following screen is displayed Supply Fan Bypass Relay NORMAL Used With Units with VFD and bypass Possible Values Normal Bypass 1 Press the NEXT key until the following screen is display...

Page 45: ...r scrolling through the Active list or after pressing the DIAGNOSTICS key when no active diagnostics are present It s used to view the past 20 diagnostics Diagnostics in this log are stacked in invers...

Page 46: ...ssure Occ Zone Heat Setpoint Return Air Temp Supply Air Pres RA Humidity OA Humidity Auto Reset SA Static Pres Limit SCM Communication Evap Temp CKT 1 2 3 4 MCM Communication Heat Module Commun ECEM C...

Page 47: ...shoot diagnostics reference the Installation Operation and Maintenance Manual SCXF SVX01 EN that ships with the Signature Series units and SCXG SVX01 EN that ships with the Modular Series units Log 1...

Page 48: ...TPOINT Suppression a parameter used for setting the ZoneTemp SETPOINT at a lower value than the mechanical cooling zone temp SETPOINT External Heat A heat source external to the self contained unit th...

Page 49: ...e Pressure The pressure in the building as measured by the Space Pressure Transducer referenced to outside atmospheric pressure Supply Air Pressure High Limit A pressure limit to prevent unit casing a...

Page 50: ...Generic Building Automation System 4 6 Glossary 48 H Heat Module 6 Human Interface 22 40 Human Interface Keypad See Figure 2 9 Human Interface Module See Figure 1 8 Hydronic Heat 48 I Independent Refr...

Page 51: ...empering 49 T TCI 5 46 Temperature Input Calibration 30 Temperature Input Offset 13 30 TEST START 9 43 TEST START Key 10 Trane Communications Interface Module TCI Option 6 U UCM 5 6 UCM Control System...

Page 52: ...controls and HVAC systems comprehensive building services and parts For more information visit www Trane com Trane has a policy of continuous product and product data improvement and reserves the rig...

Reviews: