SCXF-SVX01Q-EN
19
Table 9. Filter data, air-cooled units models SCRF & SIRF (continued)
Unit size
20- 35 tons
40-60 tons
Number - Size (in.)
4 - 16 x 20
4 - 25 x 20
4 - 20 x 20
2 - 20 x 20
4 - 18 x 20
8 - 25 x 16
N/A
4 - 20 x 16
Table 10.
Self-contained heating coil
Unit Size
SCWF 20 - 38
SCWF 42 - 80
SCRF 20 - 35
SCRF 40 - 60
Steam Coil
Coil Type
NS
NS
NS
NS
Rows
1
1
1
1
No./Size (inches)
(2) 24 x 58
(2) 30 x 81
(2) 24 x 58)
(2) 30 x 81
No./Size (mm)
(2) 609.6 x 1473.2
(2) 762 x 2057.4
(2) 609.6 x 1473.2
(2) 762 x 2057.4
FPF
42
42
42
42
Hot Water Coil
Coil Type
5W
5W
5W
5W
Rows
1 or 2
N/A
N/A
N/A
No./Size (inches)
(2) 24 x 58
(2) 30 x 81
(2) 24 x 58
(2) 30 x8 1
No./Size (mm)
(2) 609.6 x 1473.2
(2) 762 x 2057.4
(2) 609.6 x 1473.2
(2) 762 x 2057.4
FPF
80 or 108
80 or 108
80 or 108
80 or 108
Notes:
1
.
Hot water and steam heating coils have Prima-Flo® fins without turbulators.
2
.
For coil capacities, use TOPSS™ (Trane Official Product Selection Program).
3
.
Full capacity coils consist of two coils stacked and piped in parallel.
Table 11.
Waterside economizer coil physical data
Model
Unit Size
Type
Rows
FPF
Height
(in)
Length
(in)
SCXF
20, 22 & 25
Chemically Cleanable
2
108
40
78.5
SCXF
20, 22 & 25
Mechanical Cleanable
2
108
40
78.5
SCXF
20, 22 & 25
Chemically Cleanable
4
108
40
78.5
SCXF
20, 22 & 25
Mechanical Cleanable
4
108
40
78.5
SCXF
29 & 32
Chemically Cleanable
2
108
55
78.5
SCXF
29 & 32
Mechanical Cleanable
2
108
55
78.5
SCXF
29 & 32
Mechanical Cleanable
4
108
55
78.5
SCXF
29 & 32
Chemically Cleanable
4
108
55
78.5
SCXF
35 & 38
Chemically Cleanable
2
108
57.5
78.5
SCXF
35 & 38
Mechanical Cleanable
2
108
57.5
78.5
SCXF
35 & 38
Chemically Cleanable
4
108
57.5
78.5
SCXF
35 & 38
Mechanical Cleanable
4
108
57.5
78.5
SCXF
42 & 46
Chemically Cleanable
2
144
55
101