114
SCXF-SVX01Q-EN
Category
Diagnostic
Unit must
be
Configured with water cooled condenser and/or water economizer and have water flow switch installed.
Time to
React
Immediate
Actions to
be Initiated
A “lockout all ckts” request is issued to the “compressor staging function”
Reset
Automatic reset occurs after water flow input returns to within range continuously for 3 seconds, water pump is requested OFF,
or water flow switch becomes not installed.
Z
Zone Cool Setpoint Failure
Problem
Occupied zone cooling setpoint is out of range.
Reason for
Diagnostic
Input designated as occupied zone cooling setpoint source is out of range (temp. < 45°F or > 94°F).
Controls
Reaction
The active occupied zone cooling setpoint reverts to the default occupied zone cooling setpoint.
Reset
Required
(PAR) an automatic reset occurs after designated occupied zone CSP input returns to its allowable range for 10 continuous
seconds, or after a different valid occupied zone CSP selection source is user-defined.