Table 17.
Airside economizer sizes and dimensions (in.) (continued)
Size
H (1)
H (2)
J
K
L
M
Weight
SXWF 42
2-1/2
15
26
24-3/4
20-3/8
63-1/2
640
SXRF 40
6-7/8
15
26
24-3/4
20-3/8
63-1/2
640
SXWF 46
6-7/8
15
26
24-3/4
20-3/8
63-1/2
640
SXRF 50
1-7/8
9-1/4
37-1/2
19
20-3/8
63-1/2
700
SXRF 60
1-7/8
9-1/4
37-1/2
19
20-3/8
63-1/2
700
SXRF 52-58
1-7/8
9-1/4
37-1/2
19
20-3/8
63-1/2
700
SXWF 65-80
1-7/8
9-1/4
37-1/2
19
20-3/8
63-1/2
800
Service Clearances
See figure and table below for recommended service
and code clearances.
Figure 14.
Top view of self-contained unit showing
recommended service and code clearances(a)
Air Inlet
See Table
42” (1066.8mm) (20-38 Ton)
Minimum
48” (1219mm) (42-110 Ton)
Control
Panel
36” (914.4mm)
Minimum
Left side
Front
Right side
N
No
otte
e:: (a) See for right side clearance values for various
unit configurations.
Table 18.
Service and code clearance requirements
Side
Distance—inches (mm)
Purpose
Front
42 (1066) (20 to 38 tons)
NEC code requirements
48 (1219) (42 to 110 tons)
Fan service/removal
Left
36 (914)
Filter, refrigeration, and waterside components
Right
9 (229)
Non VFD w/open return
18 (457)
Non VFD w/ducted return
9 (229)
20 to 80 tons, w/VFD 7.5 to 50 hp
36 (914)
90 to 110 tons (motor, condensers, and refrigeration)
Inlet
18 (457) (20 to 80 tons)
Provides uniform airflow
36 (914) (90 to 110 tons)
Provides uniform airflow
Summary of Contents for IntelliPak SCRF 25