11
Nomenclature and Performance Data
High-efficiency Model (H type)
1. The cooling capacity is measured in the conditions of water outlet at 7
℃
and air inlet at the ambient temperatureof 35
℃
.
2. The heating capacity is measured in the conditions of water outlet at 45
℃
and air inlet at the ambient dry bulb temperature of 7
℃
and the
wet bulb temperature of 6
℃.
.
Model
CXAJ065
CXAJ130
CGAJ065
CGAJ130
Cooling
Rated Cooling Capacity
kW
65
130
65
130
Rated Input Power
kW
21.0
40.9
21.0
40.9
Rated Operating Current
A
41
78.0
41
78.0
Heating
Rated Heating Capacity
kW
67
137
-
-
Rated Input Power
kW
21.5
40.0
-
-
Rated Operating Current
A
41
71.0
-
-
Max.
Operating
Max. Input Power
kW
29.2
57.2
29.2
57.2
Max. Current
A
55.0
98.2
55.0
98.2
Compressor
Category
Hermetic scroll
No.
Pieces
2
4
2
4
Rated Cooling Power
kW
9.2
9.2
9.2
9.2
Rated Cooling Current
A
18
18
18
18
Rated Heating Power
kW
9.1
9.1
-
-
Rated Heating Current
A
18
18
-
-
Refrigerant
Category
R410A
Charge
kg
15
15*2
15
15*2
Water Side
Category of Heat Exchanger
High-efficiency shell-tube heat exchanger
Rated Water Flow
CMH
11.2
22.4
11.2
22.4
Water Pressure Drop
kPa
60
70
60
70
Connections
mm
DN125
DN125
DN125
DN125
Air Side
Category of Heat Exchanger
High-efficiency fin-coil heat exchanger
Fan No.
Pieces
2
2
2
2
Rated Input Power of Fan
kW
0.75
1.5
0.75
1.5
Rated Current of Fan
A
2.1
3.96
2.1
3.96
Air Flow
CMH
12000
20000
12000
20000
Unit
Power Supply
V/PH/Hz
380/3N~/50
Noise
dB(A)
69
70
69
70
Net Weight
kg
730
1150
730
1150
Operating Weight
kg
800
1250
800
1250
Dimension
Length
mm
2145
2400
2145
2400
Width
mm
1000
1200
1000
1200
Height
mm
2155
2380
2155
2380