96/115
V07-19.0
Parameter
Value
Description
Termination
Enable the termination resistor of the bus line [Passive]
Baud rate
Baud rate setting [76800]
MX info frame
MX info frame setting [1]
Max master
Max master setting [18]
General:
Module configuration/info
Software version
Display software version
Device ID
Display device ID
Module
Display module information
Diagnostics
Display diagnostic information from the module
Use default
Active
Set back to the default settings
Table 38:
BACnet MS/TP configuration
22.2.3
BACnet IP
Parameter
Value
Description
State
Display hardware state of the module
Comm failure
Display communication error
Passive
No communication error
Active
Communikation error
BACnet:
Configuration of the BACnet side
Device name
Device name setting [POL908_......]
Device ID
Device ID setting [4194303]
Port
Communication port setting [47808]
Imperial unit
system
Use of imperial unit system [Passive]
Passive
Metric unit system
Active
Imperial unit system (inch, °F, …)
Unicode
Enable Unicode [Passive]
Description
language
Description language setting for data point list [English]; do not change it!!
Security level
Security level setting [0]
Alarm server ID
Alarm server ID setting [1]
Alarm device ID1
Alarm device ID1 setting [0]
Alarm device ID2
Alarm device ID2 setting [0]
Alarm device ID3
Alarm device ID3 setting [0]
Comm mapping
Used mapping setting [16384 = COM1]; do not change it!!
TCP/IP:
IP-interface configuration