Description
R/W
Modbus
BACnet
LON
AHU: digital outputs
0=Supply fan 1
1= Return fan 1
2=Pump/enable heat recovery
3=Pump heating battery 1
4=Pump heating battery 2
5=Pump cooling battery 1
6=Stage 1 electric battery
7=Humidifier pump/enable humidifier
8=Humidifier filling valve
9=Humidifier draining valve
10=Fresh/Exhaust damper
11=AHU Run
12=AHU Alarm
13=AHU Warning
14=Cool/Heating mode
15=Winter/Summer mode
R
I310
AHU_OutSta1
SupplyFan_Stage
ReturnFan_Stage
HeatRec_Pump
HeatBatt1_Pump
HeatBatt2_Pump
CoolBatt1_Pump
-
Humidifier_Pump
Hum_FillVlv
Hum_DrainVlv
SuEx_Dmp
AHU_Run
AHU_Alarm
AHU_Warning
AHU_CoolHeat
WinSumSwitch
nvoDO
Bit 0..15
0=Hardware contact operation mode
R
I311
AHU_OutSta2
HW_OPMFix