102/115
V07-19.0
Description
R/W
Unit
Modbus
BACnet
LON
Supply speed smoke fan
R/W
0.1 %
H90
Set_SupplySpeedSmoke
Supply speed fireman fan
R/W
0.1 %
H91
Set_SupplySpeedFire
Return speed smoke fan
R/W
0.1 %
H109
Set_ReturnSpeedSmoke
Return speed fireman fan
R/W
0.1 %
H110
Set_ReturnSpeedFire
Supply fan request value
R
0.1 %
H34
SupplyFanSpeed
Return fan request value
R
0.1 %
H35
ReturnFanSpeed
Supply fan request stage
0=-, 1=Off, 2=Stage 1, 3=Stage 2, 4=Stage 3
R
0..4
H36
SupplyFanStage
Return fan request stage
0=-, 1=Off, 2=Stage 1, 3=Stage 2, 4=Stage 3
R
0..4
H37
ReturnFanStage
Fan control with air flow control:
Supply airflow rate for Eco mode
(1)
R32/W32
m³/h
H10
Set_SupplyFlowEco
nviPress_Flow00
Supply airflow rate for Comfort mode
(1)
R32/W32
m³/h
H12
Set_SupplyFlowCmf
nviPress_Flow01
Supply airflow rate for Night Setback mode
(1)
R32/W32
m³/h
H18
Set_SupplyFlowNht
nviPress_Flow04
Return airflow rate for Eco mode
(1)
R32/W32
m³/h
H14
Set_ReturnFlowEco
nviPress_Flow02
Return airflow rate for Comfort mode
(1)
R32/W32
m³/h
H16
Set_ReturnFlowCmf
nviPress_Flow03
Return airflow rate for Night Setback mode
(1)
R32/W32
m³/h
H20
Set_ReturnFlowNht
nviPress_Flow05
Maximum supply airflow rate from air quality control
(1)
R32/W32
m³/h
H22
Set_SupplyFlowQAirMax
Maximum return airflow rate from air quality control
(1)
R32/W32
m³/h
H24
Set_ReturnFlowQAirMax
Maximum supply airflow rate from dehumidification
(1)
R32/W32
m³/h
H30
Set_SupplyFlowDeHumMax
Maximum return airflow rate from dehumidification
(1)
R32/W32
m³/h
H32
Set_ReturnFlowDeHumMax
Supply airflow rate – request from air quality control
(1)
R32
m³/h
H106
SupplyFlowQAir