88/115
V07-19.0
Setting
Description
Default
Sort order 1
1st sort order criteria
Time
Sort order 2
2nd sort order criteria
Time
Descending order
Last occurred alarm on the top of the list
Passive
Alarm history:
Reset
Clear the entire alarm list
Sort order 1
1st sort order criteria
Time
Sort order 2
2nd sort order criteria
Time
Descending order
Last occurred alarm on the top of the list
Active
Table 31:
Alarm lists configuration
Sort order
Description
Default
Time
Sort by date / time
ID
Sort by alarm ID
Class
Sort by alarm class Danger, High(A), Low(B)
or Warning (C)
State
Sort by state (error type)
Table 32:
Sort order configuration for the alarm lists
21.5 Alarm index
The following table shows possible error messages, which consist of a text for the part of the AHU
and a text for the alarm (alarm type) itself.
Message
Description
Alarm class
Outdoor temp.
The outdoor temperature sensor is broken
Call the service engineer for the replacement
of the sensor
Low(B)
Supply temp.
The supply air temperature sensor is broken;
AHU stops
Call the service engineer for the replacement
of the sensor
Danger
Return temp.
The return air temperature sensor is broken;
AHU stops
Call the service engineer for the replacement
of the sensor
Danger
Saturation temp.
The saturation temperature sensor is broken
Call the service engineer for the replacement
of the sensor
High(A)
Room temp.
The room temperature sensor is broken
Call the service engineer for the replacement
of the sensor
High(A)