BAS-SVX45F-GB
25
Wiring and Powering the Tracer UC600
Wiring AC Power to Tracer UC600
1.
Connect both secondary wires from the 24 Vac transformer to the XFMR terminals on the
device.
2. Ensure the device is properly grounded.
Important: This device must be grounded for proper operation!
The factory-supplied
ground wire must be connected from any chassis ground connection on the device to
an appropriate earth ground (
). The chassis ground connection used may be the 24
Vac transformer input at the device, or any other chassis ground connection on the
device.
Note:
The device is not grounded through the DIN rail connection.
Figure 7.
Wiring AC power to the transformer
AO
6
UI
14
AO
5
UI
13
AO
4
UI
12
AO
3
UI
11
AO
2
UI
10
AO1
UI
9
BO
4
BO
3
BO
2
BO
1
RELAYS
0.5 A MAX
IMC
1
IMC
P
1
UI
8
UI
7
UI
6
UI
5
UI
4
UI
3
UI
2
UI
1
IMC
+24
VDC
LINK
OUT
+24
VDC
+24
VDC
OUT
24
VAC
MBUS
OUT
24
VAC
XFMR
24
VAC
SERVICE TOOL
SERVICE
LINK
ACT
IMC
MBUS
LINK
RX
TX
UC
600
ADDRESS
0 1
2
3
4
5
6
7
8
9
x1
0 1
2
3
4
5
6
7
8
9
x10
0 1
2
3
4
5
6
7
8
9
x100
BO
4
BO
3
BO
2
BO
1
24 VAC
transformer
Note
: A pigtail connection should be used
between the chassis ground on the device
and an earth ground, if the device is not
grounded through one leg of the
transformer wiring.