Wiring Inputs and Outputs
Wiring Binary Outputs
The UC600 has four binary outputs that are used as powered outputs.
Notice:
Controlling coil-based loads: Inrush current (the initial surge of a current into a load before it attains
normal operating condition) can be three times greater, or more, than the operating current.
Important:
Use pilot relays for dry contact outputs for load currents greater than 0.5 amperes and
use powered outputs for load currents less than 0.5 amperes.
1.
Connect the shield to a common terminal at the terminal board and tape it back at the powered
output device.
2. Connect the signal wire to an available output terminal.
3. Use the Tracer TU service tool to configure the binary output for binary operation.
Figure 16. Typical wiring, relays (binary outputs)
AO
6
UI
14
AO
5
UI
13
AO
4
UI
12
AO
3
UI
11
AO
2
UI
10
AO1
UI
9
BO
4
BO
3
BO
2
BO
1
RELAYS
0.5 A MAX
IMC
1
IMC
P
1
UI
8
UI
7
UI
6
UI
5
UI
4
UI
3
UI
2
UI
1
IMC
+24
VDC
LINK
OUT
+24
VDC
+24
VDC
OUT
24
VAC
MBUS
OUT
24
VAC
XFMR
24
VAC
SERVICE TOOL
SERVICE
LINK
ACT
IMC
MBUS
LINK
RX
TX
UC
600
ADDRESS
0 1
2
3
45
6
7
8
9
x1
0 1
2
3
45
6
7
8
9
x10
0 1
2
3
45
6
7
8
9
x100
BO
4
BO
3
BO
2
BO
1
Pilot relay
(24 VAC coil)
Powered
output
Tape back shield
Common
Common
Signal
Signal