INSTALLER'S GUIDE
Important: The BAYEV* electric heat accessory may include up to a combination of three 30 and/or 60 amp circuit break-
ers to provide an electrical disconnect for service personnel that is intended to help protect internal electrical components
in the event of a short circuit or ground fault. As designed, the circuit breakers supplied in the BAYEV* accessory
DO NOT
provide overcurrent protection of the branch circuit. Therefore, the branch circuit(s) shall be sized and protected according
to the unit nameplate.
Control Board Jumper Settings
When the heater comes from the factory, the jumper will be
in the PARK position. The board is already configured for the
heater size that is required, so no adjustments are necessary.
NOTE: If the jumper is moved to another kW rating and
power is applied, the factory programming on the PARK
position is lost. The jumper must then be applied to the
appropriate rating per the heater model number.
Heater Data
Table 3.1 BAYEV -- HEATER DATA
Heater Model No.
Number of
Circuits
240 VOLT
208 VOLT
Capacity
Heater Amps
per Circuit
Capacity
Heater Amps
per Circuit
kW
BTUH
kW
BTUH
BAYEVAC05BK1AA
1
4.80
16400
20
3.60
12300
17.3
BAYEVAC05LG1AA
1
4.80
16400
20
3.60
12300
17.3
BAYEVAC08BK1AA
1
7.68
26200
32
5.76
19700
27.7
BAYEVAC08LG1AA
1
7.68
26200
32
5.76
19700
27.7
BAYEVAC10BK1AA
1
9.60
32800
40
7.20
24600
34.6
BAYEVAC10LG1AA
1
9.60
32800
40
7.20
24600
34.6
BAYEVBC15BK1AA
2
14.40
49200
40/20
10.80
36900
34.6/17.3
BAYEVBC20BK1AA
2
19.20
65600
40/40
14.40
49200
34.6/34.6
BAYEVAC10LG3AA
1-3 PH
9.60
32800
23.1
7.20
24600
20.0
BAYEVBC15LG3AA
1-3 PH
14.40
49200
34.6
10.80
36900
30.0
BAYEVCC25BK1AA
3
24.00
82000
40/40/20
18.00
61500
34.6/34.6/17.3