Installation
Air Flow Adjustment
Note:
(6 through 25 ton units ONLY)
To increase CFM, loosen the turns
open set screw on the sheave, and
turn the sheave clockwise.
To decrease CFM, Loosen the turns
open set screw on the sheave, and
turn the sheave counterclockwise.
To increase belt tension, loosen the
adjustment bolt and pull motor
mounting plate back until the belt is
tight. Tighten the adjustment bolt
after the belt has reached the desired
tension.
See
Figure 69
for fan motor and
sheave adjustment.
WARNING
Rotating Components!
Disconnect all electric power,
including remote disconnects before
servicing. Follow proper lockout/
tagout procedures to ensure the
power can not be inadvertently
energized. Failure to disconnect
power before servicing could result
in death or serious injury.
Figure 69.
Fan motor and sheave
adjustment
BELT
ADJUSTMENT
BOLT AND PLATE
FAN SHEAVE
Waterside Economizer
Installation
Note:
for GEH 1/2 to 5 ton units
WARNING
Hazardous Voltage!
Disconnect all electric power,
including remote disconnects before
servicing. Follow proper lockout/
tagout procedures to ensure the
power can not be inadvertently
energized. Failure to disconnect
power before servicing could result
in death or serious injury.
WARNING!
Grounding Required!
Follow proper local and state
electrical code on requirements for
grounding. Failure to follow code
could result in death or serious
injury.
The following steps were sequenced
to aid in the installation and mating
of a water side economizer to a
water-source heat pump (GEH 1/2 to
5 ton).
1.
Remove the control side service
panel of the water-source heat
pump unit.
2.
Remove rubber isolation
grommets from the return-air
section. Place them in a
convenient location.
3.
Attach ducted panel to the water-
source heat pump unit with six
factory provided Torx® head
screws. This panel is shipped
loose with the water-source heat
pump but must be field installed
to the unit.
4.
Attach the water side
economizing unit to the ducted
panel of the water-source heat
Figure 70.
Step 3
pump with 10-factory provided
Torx® head screws. The
economizing package fits to the
outside of the of the water-
source heat pump. Trane
recommends the mating of the
systems be made via 3-screws
spaced evenly across the top, 3-
screws spaced evenly across the
bottom (installed immediately
after hanging the unit), and 2-
screws on each side.
5.
Install the 18-inch steel braided
hose between the upper most
piping connection of the
economizer, and the water-in of
the heat pump. The hose is
shipped loose with the water-
side economizer.
Figure 71.
Step 4
Figure 72.
Step 5
Summary of Contents for Axiom GEHB 006
Page 88: ...88 WSHP SVX01E EN Figure 1 Basic 208 V 60 Hz 1Ph Wiring...
Page 89: ...WSHP SVX01E EN 89 Wiring Figure 2 Deluxe 380 420 V 50 Hz 3 Ph...
Page 90: ...90 WSHP SVX01E EN Wiring Figure 3 ZN510 208 V 60 Hz 1 Ph...
Page 91: ...WSHP SVX01E EN 91 Wiring Figure 4 ZN524 460 V 60 Hz 3 Ph...
Page 95: ......