WSHP-SVX01E-EN
51
Installation
Dual Filtration (GEH 1/2
to 5 ton)
Note:
The dual-filtration design is
typically used in a free-return
application.
The horizontal, GEH model, allows
the installer flexibility in design
applications such as a dual filtration
option. With the dual filtration
design, the unit will contain a lower
static which translates into a
decrease in filter maintenance. For
installation of a dual filtration
accessory for the GEH model, verify
that an extra set of return-air filter
racks and filter have been ordered
from the factory. This accessory will
be shipped separate from the unit,
and should be located in a separate
box than the unit.
1.
Remove the return-air side panel
from the GEH unit. This panel is
held in place by six Torx® head
screws.
2.
Install the top/bottom filter rack
at the new opening. The 1"/2"
(25.4/50.8 mm) adjustable filter
rack is held in place with four
Torx® head screws that once
held the panel.
Figure 48.
Take off side panel
Figure 49.
Install top/bottom filter
rack
3.
Install the 1"/2" (25.4/50.8 mm)
filter.
Return-Air Duct Panel
Note:
The ducted panel design is
typically used in combination
with a field installed ceiling
filter rack design.
The return-air arrangement may be
easily converted from a free return-
air system, to a ducted return-air
system with the addition of a return-
air side panel on the GEH unit. By
replacing the filter racks with the
return-air panel, a complete seal
from the ductwork to the unit is
possible. The 1 1/2" (38 mm) duct
flange facilitates ease of field hook-
up to the mechanical system.
1.
Install the return-air duct panel to
the return-air opening with the
six Torx® head screws provided
for the filter rack assembly.
Figure 50.
Install filter
Table 31. Opening size and part number
Unit Size
60 HZ
Unit Size
50 HZ
A
B
Duct Collar
Part Number
006-015
006-012
17 1/2" (445) 13" (330)
4474 1133 0100
018-030
015-024
20 1/2" (521) 15" (381)
4474 1134 0100
036-042
030-036
22 1/2" (572) 17" (432)
4474 1135 0100
048-060
042-060
26 1/2" (673) 19" (483)
4474 1136 0100
Figure 51.
Install return air duct
panel
DUCT PANEL
w
i
th 1 1/2"-FLANGE
A
Un
i
t S
i
de
Un
i
t S
i
de
Un
i
t Top
Un
i
t To
p
B
1"
3 3/4
"
Summary of Contents for Axiom GEHB 006
Page 88: ...88 WSHP SVX01E EN Figure 1 Basic 208 V 60 Hz 1Ph Wiring...
Page 89: ...WSHP SVX01E EN 89 Wiring Figure 2 Deluxe 380 420 V 50 Hz 3 Ph...
Page 90: ...90 WSHP SVX01E EN Wiring Figure 3 ZN510 208 V 60 Hz 1 Ph...
Page 91: ...WSHP SVX01E EN 91 Wiring Figure 4 ZN524 460 V 60 Hz 3 Ph...
Page 95: ......