62
WSHP-SVX01E-EN
Installation
the heat pump to the 3-way
valve’s wire harness.
15. Connect the factory installed
wire harness to the to the wire
harness supplied with the 3-way
valve.
16. Bundle excess valve wire, and
wire tie the bundle neatly.
17. Install control side service panel
to the heat pump.
18. Install the unit filter frame to the
economizing inlet.
19. Insulate the economizing piping
package with field supplied pipe
insulation. Insulating the piping
will help stop condensation from
forming on the pipe.
Note:
Trane does not provide
insulation on the
economizing piping package.
This insulation must be field
provided and field installed.
20. Install waterside service panel to
the heat pump.
21. Field pipe the drain lines of the
waterside economizer and water-
source heat pump together prior
to installing a condensate trap.
See page
52
for proper trapping
of condensation. The economizer
condensate line must be trapped
prior to the unit’s drain line. This
helps prevent air from being
sucked through the drain line
causing condensate to spit or
build-up in the economizer or
unit drain pans.
Table 39.
Actuator
Wire # Color
Factory Harness
Wire # Color
1 BLK
=
25L-Black
2 WHT
=
23T-White
3 WHT
=
73A-White
Summary of Contents for Axiom GEHB 006
Page 88: ...88 WSHP SVX01E EN Figure 1 Basic 208 V 60 Hz 1Ph Wiring...
Page 89: ...WSHP SVX01E EN 89 Wiring Figure 2 Deluxe 380 420 V 50 Hz 3 Ph...
Page 90: ...90 WSHP SVX01E EN Wiring Figure 3 ZN510 208 V 60 Hz 1 Ph...
Page 91: ...WSHP SVX01E EN 91 Wiring Figure 4 ZN524 460 V 60 Hz 3 Ph...
Page 95: ......