4. The limitation of the EEV opening
State of the unit
Requirement of the opening
Lower limit
Upper limit
Shut down
Standard opening of the model, according to the
opening of last time
/
/
Standby
(temperature sensor off)
Standard opening of the model, according to the
mode before the temperature sensor is off
/
/
Cooling startup process
Execute the standard cooling opening of the model
Standard opening
400
Heating startup process
Execute the standard heating opening of the model
150
400
Cooling, dehumidification
Adjust automatically
70
470
Heating
Adjust automatically
70
470
Defrosting
Fixed opening
200
400
Oil return
Fixed opening
150
400
Refrigerant discharge
Fixed opening
150
400
9.4.6 Control of shutdown
1. Initiative shutdown mode (shutdown normally without protection)
When the air conditioner is in cooling or heating mode, the compressor get the shutdown signal, the current
frequency of the compressor is more than 55HZ (EE) , the compressor will decrease to 48HZ at the speed of
2HZ/s and shut down directly.
If the current frequency of the compressor is lower than 55HZ, it will shut down directly after it receives the
signal. Avoid that the sudden shutdown will cause too strong stress when in high working frequency.
After the compressor stops, the fan motor will execute the left heat blowing and then stops.
Shutdown because of the anti-freeze protection, the compressor will stop as initiative shut down mode/
2. Passive shut down mode (Error protection shut down)
When the system come to the pressure protection, over-current protection, high module temperature protection,
high condensation temperature protection and the unit shut down, no matter the frequency of the compressor
come to 55HZ, the unit will shut down directly.
9.4.7 Defrosting control in heating mode
In heating mode, condenser heat exchanger defrosting condition is detected by outdoor coil temperature
sensor, and defrosting is controlled by outdoor ambient temperature and coil temperature.
1. Defrosting starting condition:
1) After compressor running in heating for continuous 10 minutes (E) and for accumulated 50 minutes (E) , by
testing Te (defrosting temp sensor) or TC (testing of outdoor exchanger frosting condition) and outdoor ambient
temp sensor TA, when it meeting the following condition for continuous 5 minutes, the unit will enter defrosting
operation. In case of no defrosting operation caused by imbalanced refrigerant flow (caused by refrigerant lack or
other reason) , the unit will enter defrosting when any one of the two conditions are meet.
Entering condition:
138
Summary of Contents for 4TXK6512G1000AA
Page 16: ...2 Dimension 2 1 Dimension 4MXC6518G1000AA 7...
Page 21: ...2 6 Dimension 4MXD6512G1000AA 1 8 5 369 8 5 0 8 9 2 420 1 0 0 0 85 6 4 0 12...
Page 23: ...13...
Page 27: ...1 10 360 2 11 Dimension4MXD6560G1000AA 1262 1200 6 0 0 6 6 0 17...
Page 28: ...1 0 0 0 6 8 2 12 Dimension4MXX6518G1000AA 230 230 2 3 1 8...
Page 29: ...2 13 Dimension4MXX6524G1000AA 19 230 230 1330...
Page 30: ...230 230 1330 2 14 Dimension4MXX6536G1000AA 2 0...
Page 33: ...2 17 Dimension4TXK6512G1000AA...
Page 34: ...23...
Page 35: ...2 18 Dimension4TXK6518G1000AA 24...
Page 36: ...2 19 Dimension4TXK6524G1000AA 25...
Page 38: ...2 21 Dimension4TXK6548G1000AA 27...
Page 39: ...1 3 3 285 3 3 5 2 22 Dimension4TXK6560G1000AA 28...
Page 48: ...0150538189 SW1 O N 1 O N 2 T1A 250VAC F U S E 2 T25A 250VAC FU S E1 4 7 4TXK6512G1000AA 3 7...
Page 75: ...6 0...
Page 79: ...6 3...
Page 82: ...m m o w m m Clamp Clamp accessory Tape White Drain hose Below4mm...
Page 87: ...6 9...
Page 95: ...7 5...
Page 101: ...8 0...
Page 109: ...87...
Page 124: ...100...
Page 129: ...104...
Page 132: ...106...
Page 139: ...112...
Page 142: ...114...
Page 144: ...115...
Page 156: ...126...
Page 159: ...0011800966AL 4TXK6518G1000AA 0011800241C 1U24RS1ERA 129...
Page 160: ...0151800349A 4TXK6536G1000AA 130...
Page 161: ...0151800054BG 4TXK6548G1000AA 0151800054BK 4TXK6560G1000AA 131...
Page 165: ...276 Common control 134...
Page 168: ...The longest 3 minutes 136 O R...
Page 186: ...154...
Page 187: ......