background image

4TWL6036A-SF-1F-EN

11

Table 1. Defrost Control Thermistor Table

TEMP °F

TEMP °C

THERMISTOR

RESISTANCE

(OHMS)

Volts DC

-15.00

-26.11

135976

2.50

-10.00

-23.33

115112

2.40

-5.00

-20.56

97745

2.29

0.00

-17.78

83247

2.17

5.00

-15.00

71108

2.05

10.00

-12.22

60916

1.93

15.00

-9.44

52333

1.81

20.00

-6.67

45076

1.69

25.00

-3.89

38927

1.56

30.00

-1.11

33703

1.45

35.00

1.67

29253

1.33

40.00

4.44

25452

1.22

45.00

7.22

22198

1.12

50.00

10.00

19405

1.02

55.00

12.78

17002

0.93

60.00

15.56

14930

0.85

65.00

18.33

13138

0.77

70.00

21.11

11586

0.70

75.00

23.89

10238

0.63

80.00

26.67

9065

0.57

85.00

29.44

8043

0.52

90.00

32.22

7150

0.47

95.00

35.00

6368

0.42

100.00

37.78

5682

0.38

105.00

40.56

5079

0.35

110.00

43.33

4548

0.31

115.00

46.11

4079

0.28

120.00

48.89

3665

0.26

125.00

51.67

3298

0.23

130.00

54.44

2972

0.21

135.00

57.22

2683

0.19

Example:

Sensor temp. = 19°F
Measured Resistance = 46K ohms
This sensor is good since the measured value is
relatively close to the chart value.

Table 2. DEMAND DEFROST QUICK SPECS

COMPRESSOR

SCROLL

SCROLL

MNEMONIC NO
CNT

CNT08177

CNT08176

GROUP NOMENCLATURE

(a)

D161244G01

D161246G02

SUPERSEDURE
CNT

07824

07825

OD FAN TYPE – PSC/ECM

PSC

ECM

1-SPD

1-SPD

DEFROST ENABLED: Y = ON
COIL TEMPERATURE

≤52 °F

(b)

≤52 °F

DEFROST PERMIT: Y = ON
COIL TEMPERATURE

≤32 °F

≤32 °F

MIN DEFROST TIME (MINUTES)

1

1

TARGET DEFROST TIME
(MINUTES)

4

4

MAX TIME OVERRIDE (MINUTES
+)

15

15

DEFROST TERMINATE COIL
TEMPERATURE (Factory Setting)

47°F

47°F

DEFROST HI TERMINATE COIL
TEMPERATURE (Cut Jumper 2)

70° F

70°F

SOV SWITCH-OVER DELAY
AFTER DEFROST TERM.
(SECONDS)

12

12

DEFEAT SWITCH-OVER DELAY
(SECONDS) (Cut Jumper 1)

0

0

LOW AMBIENT HEAT PUMP LOCK
OUT

-12°F

-12°F

LOW AMBIENT HEAT PUMP
RESUME

-3

-3

LPCO INPUT TO CONTROL

YES

YES

LPCO BYPASS IN/OUT DEFROST
(MINUTES)

3

3

(a)

GROUP suffix for drawing number D

(b)

≤ (EQUAL OR LESS THAN)

Table 3. LED FAULT CODES

LED

FAULT

CODES

FAULT DESCRIPTION

DEFROST

CONTROL

BEHAVIOR

1 FLASH

Ambient Temp Sensor is out
of range (open/shorted)

Initiate defrost after
every 60 minutes of
runtime. Defrost will
terminate on coil
temp. See Note 1 & 2.

2 FLASH

Coil Temp Sensor is out of
range (open/shorted)

Initiate a 15 minute
forced defrost after
every 60 minutes of
runtime. See Note 1 &
2.

3 FLASH

Low Pressure Switch is open

3 flash goes away
when/if LPCO closes.

4 FLASH

Hard Lock Out (can only be
cleared with a low voltage
power cycle)

Occurs after 9

th

trip

of LPCO. See Note 6.

D

De

effrro

osstt C

Co

on

nttrro

oll

Summary of Contents for 4TWL6036A1000A

Page 1: ...orking on the equipment observe all precautions in the literature and on the tags stickers and labels that are attached to the equipment May 2020 4 4T TW WL L6 60 03 36 6A A S SF F 1 1F F E EN N Side...

Page 2: ...ro op pe er r p pr ro oc ce ed du ur re es s c ca an n r re es su ul lt t i in n p pe er rs so on na al l i il ll ln ne es ss s o or r i in nj ju ur ry y o or r s se ev ve er re e e eq qu ui ip pm me...

Page 3: ...rd 270 c Calculated in accordance with Natl Elec Codes Use only HACR circuit breakers or fuses d This value shown for compressor RLA on the unit nameplate and on this specification sheet is used to co...

Page 4: ...4 4TWL6036A SF 1F EN Wiring Figure 1 2 0 3 0 3 5 Ton Models d159503p02...

Page 5: ...4TWL6036A SF 1F EN 5 Figure 2 2 0 3 0 3 5 Ton Models W Wi ir ri in ng g...

Page 6: ...6 4TWL6036A SF 1F EN Refrigerant Circuit Diagrams Figure 3 3 0 and 3 5 Ton Models Dwg D158717_RevB...

Page 7: ...r the pressure Again wait 20 minutes for the system conditions to stabilize before adjusting charge again 8 When system is correctly charged you can refer to System Pressure Curves to verify typical p...

Page 8: ...11 215 65 211 215 218 222 225 229 232 70 229 232 236 240 243 247 251 75 247 251 255 259 263 267 271 80 267 271 275 279 283 287 291 85 287 291 296 300 304 309 313 90 309 313 318 322 327 331 336 95 331...

Page 9: ...HART INTERCONNECTING LINES GAS 7 8 O D LIQUID 3 8 O D DWG NO 4TWL6036A1 110 115 120 125 130 135 140 145 150 155 160 165 170 40 60 80 100 120 200 250 300 350 400 450 500 550 40 60 80 100 120 1 1 3 3 5...

Page 10: ...COMMON Shorting any of the other pins to this pin causes the function of the other pin to be executed Leaving this pin open results in the normal mode of operation 2 FRC_DFT Forced Defrost Short TEST_...

Page 11: ...PERSEDURE CNT 07824 07825 OD FAN TYPE PSC ECM PSC ECM 1 SPD 1 SPD DEFROST ENABLED Y ON COIL TEMPERATURE 52 F b 52 F DEFROST PERMIT Y ON COIL TEMPERATURE 32 F 32 F MIN DEFROST TIME MINUTES 1 1 TARGET D...

Page 12: ...nitiate an Adaptive Timed Limp Mode This will be accompanied by a 1 flash The DFC will initiate defrost after 60 minutes of accumulated heating runtime and force a defrost which will terminate on coil...

Page 13: ...ram located on the inside of the control box cover Table 5 High Voltage Disconnect Switch W WA AR RN NI IN NG G H HI IG GH H L LE EA AK KA AG GE E C CU UR RR RE EN NT T F Fa ai il lu ur re e t to o f...

Page 14: ...HEAT Pink Black White X2 O Y With TAM 4 5 7 9 Thermostat Air Handler Outdoor Unit R G B W1 W2 R B O YO YO X2 R G B C O Yl W Blue O Yl 24 VAC HOT FAN 24 VAC Common SOV COOL HEAT 1st STAGE HEATING 2nd S...

Page 15: ...ng Value ________________________ F 107 F Table 9 Verify Performance 4 Refer to System Pressure Curves in the Service Facts document to verify typical performance PRESSURE CURVE SAMPLE Cooling 1450 SC...

Page 16: ...the Liquid Gage Pressure is higher than the chart value 107 F Table 11 System Information 9 Record system pressures and temperatures after charging is complete Outdoor model number ___________________...

Page 17: ...NCEL 2 Turn on electrical power disconnect s to apply power to the indoor and outdoor units ON OFF 3 Wait one 1 hour before starting the unit if compressor crankcase heater accessory is used and the O...

Page 18: ...ltage present at contactor coil Replace contactor Check control transformer and control fuse Is the control transformer and fuse good Jumper R to Y low voltage terminals at thermostat sub base Does th...

Page 19: ...4TWL6036A SF 1F EN 19 Troubleshooting Does a resistance check show an open circuit between R and S...

Page 20: ...ified mark indicates Trane U S Inc participation in the AHRI Certification program For verification of individual certified products go to ahridirectory org Trane has a policy of continuous data impro...

Reviews: