background image

4TWL6036A-SF-1F-EN

7

Subcooling Charging in Cooling between 55° F and 120°
OD Ambient

Trane has always recommended installing Trane
approved matched indoor and outdoor systems.

The benefits of installing approved indoor and outdoor
split systems are maximum efficiency, optimum
performance and the best overall reliability.

The following charging methods are therefore
prescribed for matched systems with indoor TXVs/
EEVs.

1. Subcooling (in the cooling mode) is the only

recommended method of charging above 55°
ambient temperatures.

2. For best results — the indoor temperature should

be kept between 70° to 80° F. Add system heat if
needed.

3. At startup, or whenever charge is removed or

added, the system must be operated for a minimum
of (20) minutes to stabilize before accurate
measurements can be made.

4. Measure Liquid Line Temperature and Refrigerant

Pressure at service valves.

5. Determine total refrigerant line length, and height

(lift) if indoor section is above the condenser.

6. Determine the Design Subcooling Charging

Temperature from the unit nameplate.

7. Locate this value in the appropriate column of the

Subcooling Charging Table. Locate your liquid line
temperature in the left column of the table, and the
intersecting liquid line pressure under your
nameplate subcool value column. Add refrigerant
to raise the pressure to match the table, or remove
refrigerant to lower the pressure. Again, wait (20)
minutes for the system conditions to stabilize
before adjusting charge again.

8. When system is correctly charged, you can refer to

System Pressure Curves to verify typical
performance.

Subcool Charging Correction
Charts

50

40

30

25

Use Design Subcooling

15

10

0

20

30

40

50

60

70

80

90

100

110

120

130

140

150

Add 1°

Add 2°

R

E

F

R

IG

E

R

A

N

T

 L

IN

E

 L

IF

T

 (

F

T

)

SUBCOOL CHARGING CHART CORRECTIONS TABLE (FOR LINE LENGTH AND RISE)

TOTAL REFRIGERANT LINE LENGTH (FT) - [ includes lift ]

Add 1°

Weigh-In Method for Charging

Weigh-In Method can be used for the initial installation,
or anytime a system charge is being replaced. Weigh-In
Method can also be used when power is not available
to the equipment site or operating conditions (indoor/
outdoor temperatures) are not in range to verify with
the subcooling charging method.

Calculating Charge Using the Weigh-In Method

STEP 1 -

Measure in feet the

distance between the outdoor unit
and the indoor unit. (Include the
entire length of the line from the
service valve to the IDU.) Subtract
10 ft from this entire length and
record on line 1.

1. Total
Line Length
(ft) – 10 ft

STEP 2 -

Enter the charge multiplier

(0.6 oz/ft). Each linear foot of
interconnecting tubing requires the
addition of 0.6 oz of refrigerant.

2. Charge
multiplier

x 0.6 oz

STEP 3 -

Multiply the total length of

refrigerant tubing (Line 1) times the
value on Step 2. Record the result on
Line 3 of the Worksheet.

3. Step 1 x
Step 2

=
_______-
____

STEP 4 -

This is the amount of

refrigerant to weigh-in prior to
opening the service valves.

4.
Refrigerant
(oz)

=
_______-
___oz

Summary of Contents for 4TWL6036A1000A

Page 1: ...orking on the equipment observe all precautions in the literature and on the tags stickers and labels that are attached to the equipment May 2020 4 4T TW WL L6 60 03 36 6A A S SF F 1 1F F E EN N Side...

Page 2: ...ro op pe er r p pr ro oc ce ed du ur re es s c ca an n r re es su ul lt t i in n p pe er rs so on na al l i il ll ln ne es ss s o or r i in nj ju ur ry y o or r s se ev ve er re e e eq qu ui ip pm me...

Page 3: ...rd 270 c Calculated in accordance with Natl Elec Codes Use only HACR circuit breakers or fuses d This value shown for compressor RLA on the unit nameplate and on this specification sheet is used to co...

Page 4: ...4 4TWL6036A SF 1F EN Wiring Figure 1 2 0 3 0 3 5 Ton Models d159503p02...

Page 5: ...4TWL6036A SF 1F EN 5 Figure 2 2 0 3 0 3 5 Ton Models W Wi ir ri in ng g...

Page 6: ...6 4TWL6036A SF 1F EN Refrigerant Circuit Diagrams Figure 3 3 0 and 3 5 Ton Models Dwg D158717_RevB...

Page 7: ...r the pressure Again wait 20 minutes for the system conditions to stabilize before adjusting charge again 8 When system is correctly charged you can refer to System Pressure Curves to verify typical p...

Page 8: ...11 215 65 211 215 218 222 225 229 232 70 229 232 236 240 243 247 251 75 247 251 255 259 263 267 271 80 267 271 275 279 283 287 291 85 287 291 296 300 304 309 313 90 309 313 318 322 327 331 336 95 331...

Page 9: ...HART INTERCONNECTING LINES GAS 7 8 O D LIQUID 3 8 O D DWG NO 4TWL6036A1 110 115 120 125 130 135 140 145 150 155 160 165 170 40 60 80 100 120 200 250 300 350 400 450 500 550 40 60 80 100 120 1 1 3 3 5...

Page 10: ...COMMON Shorting any of the other pins to this pin causes the function of the other pin to be executed Leaving this pin open results in the normal mode of operation 2 FRC_DFT Forced Defrost Short TEST_...

Page 11: ...PERSEDURE CNT 07824 07825 OD FAN TYPE PSC ECM PSC ECM 1 SPD 1 SPD DEFROST ENABLED Y ON COIL TEMPERATURE 52 F b 52 F DEFROST PERMIT Y ON COIL TEMPERATURE 32 F 32 F MIN DEFROST TIME MINUTES 1 1 TARGET D...

Page 12: ...nitiate an Adaptive Timed Limp Mode This will be accompanied by a 1 flash The DFC will initiate defrost after 60 minutes of accumulated heating runtime and force a defrost which will terminate on coil...

Page 13: ...ram located on the inside of the control box cover Table 5 High Voltage Disconnect Switch W WA AR RN NI IN NG G H HI IG GH H L LE EA AK KA AG GE E C CU UR RR RE EN NT T F Fa ai il lu ur re e t to o f...

Page 14: ...HEAT Pink Black White X2 O Y With TAM 4 5 7 9 Thermostat Air Handler Outdoor Unit R G B W1 W2 R B O YO YO X2 R G B C O Yl W Blue O Yl 24 VAC HOT FAN 24 VAC Common SOV COOL HEAT 1st STAGE HEATING 2nd S...

Page 15: ...ng Value ________________________ F 107 F Table 9 Verify Performance 4 Refer to System Pressure Curves in the Service Facts document to verify typical performance PRESSURE CURVE SAMPLE Cooling 1450 SC...

Page 16: ...the Liquid Gage Pressure is higher than the chart value 107 F Table 11 System Information 9 Record system pressures and temperatures after charging is complete Outdoor model number ___________________...

Page 17: ...NCEL 2 Turn on electrical power disconnect s to apply power to the indoor and outdoor units ON OFF 3 Wait one 1 hour before starting the unit if compressor crankcase heater accessory is used and the O...

Page 18: ...ltage present at contactor coil Replace contactor Check control transformer and control fuse Is the control transformer and fuse good Jumper R to Y low voltage terminals at thermostat sub base Does th...

Page 19: ...4TWL6036A SF 1F EN 19 Troubleshooting Does a resistance check show an open circuit between R and S...

Page 20: ...ified mark indicates Trane U S Inc participation in the AHRI Certification program For verification of individual certified products go to ahridirectory org Trane has a policy of continuous data impro...

Reviews: