background image

Page 24 

                 

Installer’s Guide

  Does the unit run and operate as described in the section on 

Sequence of Operation in response to the room thermostat?

 Are the condenser fan and indoor blower operating correctly  

  with proper rotation and without undue noise?

 Is the compressor operating correctly and has the system been  

  checked with a charging chart?

 Has the voltage and running current been checked to deter 

  mine if it is within limits?

 Has the thermostat been checked for calibration and the air    

discharge grilles adjusted to balance the system?

 Has the ductwork been checked for air leaks and 

 condensation?

 Has the furnace manifold pressure been checked and 

  adjusted if necessary?

 Has the heating air temperature rise been checked?

 Has the unit been checked for tubing and sheet metal rattles?   

  Are there any other unusual noises to be checked?

 Are all covers and panels in place and properly fastened?

 Has the owner been instructed on the proper operation and 

  maintenance of the unit? Be sure to leave this manual with the  
 owner.

Final Installation Checklist

 

b. The pressure switch is closed.

 

c.  The gas valve opens and the ignitor lights the burner.

 

d. Allow the thermostat to cycle on and off a few times in 

Emergency Heat mode to check out the control system 
and burner operation characteristics.  For the *CONT802 
and *CONT803 Comfort Controls if the call for heat lasts 
longer than 10 minutes, these controls will transition to 
high fire automatically. 

  3. With the burners operating, check the manifold pressure with 

a manometer. Do not exceed recommended pressures.

  4. Adjust the unit to obtain an air temperature rise with that 

specified on the unit nameplate.

 5.

 

NOTE

: For manifold pressures and orifice sizes for gas with 

other BTU ratings, contact the local gas utility.  Manifold 

pressure should be 1.8  (low) to 3.5 (high)  inches water 

column  (+0.1).  Input must 

not

 exceed the value shown on 

the nameplate.

  6. Set the thermostat at the desired temperature setting and the 

unit will function automatically.

 

Starting the Unit in the Gas Heating Mode

1.   Check to make sure all grilles and registers are open and all 

unit access doors are closed before start-up.

  2. Purge the gas supply line of air by opening the union ahead 

of the unit.  When the odor of gas is detected, retighten the 
union and wait five (5) minutes before proceeding.

 3. Open the main gas valve(s) and turn on the unit power 

supply.  

  4. Set the thermostat mode to Emergency Heat and adjust the 

heating setpoint slightly above the room temperature.

 5. The combustion blower motor should energize. The main 

burners should light within 20-25 seconds. Initial start may be 
delayed somewhat if the unit has not been purged and air is 
trapped in the gas line.

   NOTE:

  Blue smoke produced by the heat exchanger during 

the initial burner firing is caused by a thin film of oil on the 

surface of the heat exchanger. This oil will burn off quickly.

6.     Allow the thermostat to cycle on and off a few times at a 

rate of not more than once every thirty (30) seconds. 
Check both the control operation and the burner operating 
conditions.

7. 

  

 Increase the heating setpoint significantly so that the 

thermostat will transition to high fire automatically.  For 
the *CONT802 and *CONT803 Comfort Controls, there is 
a 10 minute delay before the transition occurs.  Make the 
following manifold pressure check on high fire.

MANIFOLD PRESSURE

  1. Connect a manometer to the pressure tap at the outlet side 

of the unit’s gas valve.  Read the manifold pressure with the 
main burners firing. See figure 16, page 17.

  2. If the manifold pressure reading does not match the value 

indicated on the unit nameplate, the unit pressure regulator 
must be adjusted as follows:

 

a. Remove the cover screw on the gas regulator located on 

the front side of the unit’s gas valve.

 

b. Turn the adjusting screw clockwise to increase manifold 

pressure or counterclockwise to decrease manifold 
pressure.

 3. Check the temperature rise during furnace operation to 

insure that it falls within the range specified on the unit 
nameplate.

SEQUENCE OF OPERATION

The following description applies to the *CONT402.  Some of 

the operational differences of the *CONT802 and *CONT803 

are described at the end of this section.

The following description applies to non-restricted mode.  

Restricted operation will be identical except that transitions 

from and to second stage (heat pump) heating to and from 

third stage (gas) heating can occur, not necessarily as 

a result of building load and equipment capacity, but as 

determined by the 

outdoor temperature changeover point 

selected by the installer at the indoor thermostat (see 

Restricted Mode described on page 19).

Call for 1st stage heating (heat pump): 

With the room thermostat set to 

HEAT 

and the fan set to 

AUTO

NO power is supplied from the room thermostate

 

"O" terminal 

to the unit switchover valve coil (SOV)

 

and the "O" terminal on 

the ECMC board. This leaves the switch-over valve (SOV) in 
the normal position for heating and is the signal for the (ECMC) 
to run at indoor fan speeds designed for heating. On a call for 
heating, power is supplied to the unit from the room thermostat 
(Y1) and (G) terminal. (Y1) provides power to the compressor 
contactor (CC), the defrost control (DFC) and the 

electronically 

  4. If the temperature rise noted is outside of the specified limits, 

adjust the indoor airflow to cause the temperature rise of the 
heat exchanger to fall within the required range.

HEATING SHUT-DOWN

Set the comfort control to OFF or adjust the heating set point to 
belowroom temperature.

Summary of Contents for 4DCZ6036

Page 1: ...erent hazards during installation and service the electrical supply must be disconnected and the main gas valve must be turned off If operating checks must be performed with the unit operating it is t...

Page 2: ...ingpressureexceedsthelimitofR 22 Proper service equipment is required Failure to use proper service tools may result in equipment damage or personal injury SERVICE Use only R 410A Refrigerant and appr...

Page 3: ...arefully before attempting to install oper ate or perform maintenance on this unit Installation and maintenance should be performed by qualified service techni cians only This unit is listed by Underw...

Page 4: ...Guide Step 2 Determine Unit Clearances Figure 1 4DCZ6036 1 of 3 Figures 1 through 6 show the unit critical dimensions NOTE The view labeled Bottom Side represents the Base as viewed looking up from u...

Page 5: ...Page 5 Installer s Guide Figure 2 4DCZ6036 2 of 3...

Page 6: ...Page 6 Installer s Guide Figure 3 4DCZ6036 3 of 3...

Page 7: ...Page 7 Installer s Guide Figure 4 4DCZ6048 through 4DCZ6060 1 of 3...

Page 8: ...Page 8 Installer s Guide Figure 5 4DCZ6048 through 4DCZ6060 2 of 3...

Page 9: ...Page 9 Installer s Guide Figure 6 4DCZ6048 through 4DCZ6060 3 of 3...

Page 10: ...fer to the Installation section for instruction on converting the supply and return airflow covers to down airflow 3 The field assembled Roof Mounting Curb BAYCURB050A or BAYCURB051A or a field fabric...

Page 11: ...clearance to combustible mate rial shall be maintained on air outlet duct Rooftop Installation Curb Mounting Convert Horizontal Airflow to Down Airflow The factory ships the unit for horizontal airflo...

Page 12: ...he unit by attaching clevis hooks pins or bolts to the unit casing casing hardware corner lugs angles tabs or flanges Failure to observe these warnings may result in equipment damage 1 Before preparin...

Page 13: ...r roof top applications using field fabricated ducts and sleeper rails rather than a curb or frame use the following procedure 1 Locate and secure the sleeper rails to the roof Three 3 sleeper rails a...

Page 14: ...drawing The manufacturer is not responsible for the unauthorized use of this drawing and expressly disclaims any liability for damages resulting from such unauthorized use Gasket Seal Spreader Bars B...

Page 15: ...rizontal Airflow Application with Frame Supply Air Return Air Roof Flashing Channel Iron Center Support Center Sup port required on all Frame Applications Angle Iron Frame Roof Flashing Return Air Ang...

Page 16: ...ise and vibration transmission Elbows with turning vanes or splitters are recommended to minimize air noise and resistance The first elbow in the ductwork leaving the unit should be no closer than two...

Page 17: ...making the gas pipe connection give serious consideration to providing the clearance necessary to remove the accesspanelsontheunit e g economizerandfilteraccesspanels NOTE In the absence of local cod...

Page 18: ...chonthegasvalveinletboss connect the gas piping to the unit Check the completed piping for leaks using a soap and water solution or the equivalent 6 After installation of the gas pipe in the unit the...

Page 19: ...Models that require 49 orifices for altitudes from 7000 8000 orifices must be changed to 50 HIGH ALTITUDE DERATE CHART NAT Altitude In Feet Inputs shown are with factory orifices 3 5 WC High Fire 1 8...

Page 20: ...ed A brief explanation of each mode follows RESTRICTED In the restricted mode of operation an outdoor temperature sensor is used to cause the unit to operate in the heat pump mode above a selected out...

Page 21: ...ns IMPORTANT Upon completion of wiring check all electrical connections including factory wiring within the unit Make sure all connections are tight Replace and secure all electrical box covers and ac...

Page 22: ...Page 22 Installer s Guide Figure 22 4DCZ6 Field Wiring Diagram 4DCZ6 FIELD WIRING DIAGRAM Y2 YL RD 2NDSTAGECOMPRESSOR 1STSTAGECOMPRESSOR CONSTANTCIRCULATION...

Page 23: ...h the compressor operating check the line voltage at the unit The voltage should be within the range shown on the unit nameplate If low voltage is encountered check the size and Step 5 Unit Startup le...

Page 24: ...ot been purged and air is trapped in the gas line NOTE Blue smoke produced by the heat exchanger during the initial burner firing is caused by a thin film of oil on the surface of the heat exchanger T...

Page 25: ...e After approximately 30 seconds the control energizes the indoor blower on high speed To maintain the indoor temperature at the desired setpoint the thermostat may operate the high fire gas heating c...

Page 26: ...fter defrost terminates when the outdoor coil should be clear of frost When the measured delta T during heating operation reaches the calculated initiate delta T the demand defrost control DFC opens t...

Page 27: ...he inside of the burners and the burner ports for deposit buildup and corrosion Wipe and brush the inside of the burner and the burner ports and then clean with a dry cloth If the deposit buildup or c...

Page 28: ...fast flashes is 3 seconds Status LED Liteport LED IGN Diagnostic Indicators Flash Codes Figure 23 ECM Fan Control ECM Fan Motor Adjustments If the airflow needs to be increased or decreased see the A...

Reviews: