background image

 

Page 19

Installer’s Guide

Air Filter Installation

The packaged unit requires an air filter.  The unit does not come 
with a factory installed filter rack in it, however, two filter frame ac-
cessories are offered that will allow the installation of a filter within 
the unit, BAYFLTR101 & BAYFLTR201. Otherwise a field supplied 
filter rack must be installed by the installer in the return  duct work. 
Refer to Table 5 to determine filter sizes for field supplied filter racks. 

*Filters must be installed in the return air system. The above square 

footages are based on 300 F.P.M. face velocity.  If permanent filters are 

used, size per mfg. Recommendation with clear resistance of 0.05" W.C.

High Altitude Installation

Unit nameplate ratings are based on equipment operation from 
sea level to 2000 feet elevation above sea level. 

No orifice changes 

required for high altitude installation, please refer to below chart for 
rating information.

 

Table 4. High Altitude Derate Chart

Table 5. Filter Sizes (field supplied filter rack)

Electrical Connections

Electrical wiring and grounding must be installed in accordance 
with local codes or, in the absence of local codes, with the National 
Electrical Code ANSI/NFPA 70, Latest Revision.

Electrical Wiring

NOTE: 

This unit is factory wired for 230V. See wiring dia-

gram in SERVICE FACTS for 208V conversion.

Figure 19. Power Wiring

NOTE:

 

For branch circuit wiring (main power supply to unit 

disconnect), determine wire size for the length of run using the 

circuit ampacity found on the unit nameplate and the N.E.C.

For  more than 3 conductors in a raceway or cable, see the 

N.E.C. for derating the ampacity of each conductor.

Run power supply 

Lines through 

weather-tight con

-

duit and secure 

to unit with strain 

relief

Unit Input

115k

2001

3000

4000 5000 6000 7000 8000

High stage

112100 104100 96200 88100 86900 85600 85100

Low stage

84000 78100 72100 66100 65100 64200 63800

90k
High stage

87700 81500 75200 69000 68000 67000 66500

Low stage

65700 61100 56400 51700 51000 50200 49900

70k
High stage

68200 63300 58500 53600 52900 52100 51800

Low stage

51100 47600 43900 40200 39600 39100 38800

60k
High stage

58500 54300 50100 46000 45300 44700 44300

Low stage

43800 40700 37600 34500 34000 33400 33200

For LP installations. Models that require #49 orifices, for 
altitudes from 7000 - 8000' orifices must be changed to #50. 

HIGH ALTITUDE DERATE CHART NAT.

Altitude (In Feet)

Inputs shown are with factory orifices @ 3.5"WC (High Fire) 
1.8"WC (Low Fire)
Natural Gas heating value of 950 btu/cuft.

Electrical Power

It is important that proper electrical power be available for the unit.  
Voltage variation should remain within the limits found on the unit 
nameplate.

Disconnect Switch

Provide an approved weatherproof disconnect within close proxim-
ity and 

within sight of the unit. 

If disconnect must be mounted 

to the cabinet, the location shown in Figure 21 should be the only 
one considered.

Over Current Protection

The branch circuit feeding the unit must be protected as shown on 
the unit nameplate.

Power Wiring

The power supply lines must be run in weather-tight conduit to the 
disconnect and into the side of the unit control box.  Provide strain 
relief for all conduit with suitable connectors. 
Provide flexible conduit supports whenever vibration transmission 
may cause a noise problem within the building structure.
1.  Remove the CONTROL/HEAT access panel. Pass the power  
  wires  through the Power Entry hole in the end of the unit.  
  See Figure 19.
2. Connect the high voltage wires to the appropriate contactor lug 

terminals. Single phase units use a two (2) pole contactor  
and three phase units use two (2) pole contactor and a Blue 
lead wire. Connect the ground to the ground lug on the chas-
sis. See Figure 20. Be sure all connections are tight. 

GROUNDING:  THE UNIT MUST BE ELECTRICALLY 

GROUNDED IN ACCORDANCE WITH LOCAL CODES OR 

THE NATIONAL ELECTRIC CODE.

NOTE: 

Unit must be grounded for ignitor to operate properly. 

Gas pipe to unit is not an adequate ground. Ground the unit 

internally as provided. 

HAZARDOUS VOLTAGE, MOVING PARTS, AND GAS
Bodily injury can result from high voltage electrical compo-
nents, fast moving fans, and combustible gas. For protection 
from these inherent hazards during installation and service, 
the electrical supply must be disconnected and the main 
gas valve must be turned off. If operating checks must be 
performed with the unit operating, it is the technician's re-
sponsibility to recognize these hazards and proceed safely.

WARNING

!

UNIT

NOMINAL

CFM

FILTER*

SIZE (Sq Ft)

FILTER

RESISTANCE 

("W.C.)

4DCZ6036

1200

4.00

0.08

4DCZ6048

1600

5.33

0.08

4DCZ6060

2000

6.67

0.08

IMPORTANT: 

Air filters and media wheels or plates shall meet the test 

requirements in UL 900.

Summary of Contents for 4DCZ6036

Page 1: ...erent hazards during installation and service the electrical supply must be disconnected and the main gas valve must be turned off If operating checks must be performed with the unit operating it is t...

Page 2: ...ingpressureexceedsthelimitofR 22 Proper service equipment is required Failure to use proper service tools may result in equipment damage or personal injury SERVICE Use only R 410A Refrigerant and appr...

Page 3: ...arefully before attempting to install oper ate or perform maintenance on this unit Installation and maintenance should be performed by qualified service techni cians only This unit is listed by Underw...

Page 4: ...Guide Step 2 Determine Unit Clearances Figure 1 4DCZ6036 1 of 3 Figures 1 through 6 show the unit critical dimensions NOTE The view labeled Bottom Side represents the Base as viewed looking up from u...

Page 5: ...Page 5 Installer s Guide Figure 2 4DCZ6036 2 of 3...

Page 6: ...Page 6 Installer s Guide Figure 3 4DCZ6036 3 of 3...

Page 7: ...Page 7 Installer s Guide Figure 4 4DCZ6048 through 4DCZ6060 1 of 3...

Page 8: ...Page 8 Installer s Guide Figure 5 4DCZ6048 through 4DCZ6060 2 of 3...

Page 9: ...Page 9 Installer s Guide Figure 6 4DCZ6048 through 4DCZ6060 3 of 3...

Page 10: ...fer to the Installation section for instruction on converting the supply and return airflow covers to down airflow 3 The field assembled Roof Mounting Curb BAYCURB050A or BAYCURB051A or a field fabric...

Page 11: ...clearance to combustible mate rial shall be maintained on air outlet duct Rooftop Installation Curb Mounting Convert Horizontal Airflow to Down Airflow The factory ships the unit for horizontal airflo...

Page 12: ...he unit by attaching clevis hooks pins or bolts to the unit casing casing hardware corner lugs angles tabs or flanges Failure to observe these warnings may result in equipment damage 1 Before preparin...

Page 13: ...r roof top applications using field fabricated ducts and sleeper rails rather than a curb or frame use the following procedure 1 Locate and secure the sleeper rails to the roof Three 3 sleeper rails a...

Page 14: ...drawing The manufacturer is not responsible for the unauthorized use of this drawing and expressly disclaims any liability for damages resulting from such unauthorized use Gasket Seal Spreader Bars B...

Page 15: ...rizontal Airflow Application with Frame Supply Air Return Air Roof Flashing Channel Iron Center Support Center Sup port required on all Frame Applications Angle Iron Frame Roof Flashing Return Air Ang...

Page 16: ...ise and vibration transmission Elbows with turning vanes or splitters are recommended to minimize air noise and resistance The first elbow in the ductwork leaving the unit should be no closer than two...

Page 17: ...making the gas pipe connection give serious consideration to providing the clearance necessary to remove the accesspanelsontheunit e g economizerandfilteraccesspanels NOTE In the absence of local cod...

Page 18: ...chonthegasvalveinletboss connect the gas piping to the unit Check the completed piping for leaks using a soap and water solution or the equivalent 6 After installation of the gas pipe in the unit the...

Page 19: ...Models that require 49 orifices for altitudes from 7000 8000 orifices must be changed to 50 HIGH ALTITUDE DERATE CHART NAT Altitude In Feet Inputs shown are with factory orifices 3 5 WC High Fire 1 8...

Page 20: ...ed A brief explanation of each mode follows RESTRICTED In the restricted mode of operation an outdoor temperature sensor is used to cause the unit to operate in the heat pump mode above a selected out...

Page 21: ...ns IMPORTANT Upon completion of wiring check all electrical connections including factory wiring within the unit Make sure all connections are tight Replace and secure all electrical box covers and ac...

Page 22: ...Page 22 Installer s Guide Figure 22 4DCZ6 Field Wiring Diagram 4DCZ6 FIELD WIRING DIAGRAM Y2 YL RD 2NDSTAGECOMPRESSOR 1STSTAGECOMPRESSOR CONSTANTCIRCULATION...

Page 23: ...h the compressor operating check the line voltage at the unit The voltage should be within the range shown on the unit nameplate If low voltage is encountered check the size and Step 5 Unit Startup le...

Page 24: ...ot been purged and air is trapped in the gas line NOTE Blue smoke produced by the heat exchanger during the initial burner firing is caused by a thin film of oil on the surface of the heat exchanger T...

Page 25: ...e After approximately 30 seconds the control energizes the indoor blower on high speed To maintain the indoor temperature at the desired setpoint the thermostat may operate the high fire gas heating c...

Page 26: ...fter defrost terminates when the outdoor coil should be clear of frost When the measured delta T during heating operation reaches the calculated initiate delta T the demand defrost control DFC opens t...

Page 27: ...he inside of the burners and the burner ports for deposit buildup and corrosion Wipe and brush the inside of the burner and the burner ports and then clean with a dry cloth If the deposit buildup or c...

Page 28: ...fast flashes is 3 seconds Status LED Liteport LED IGN Diagnostic Indicators Flash Codes Figure 23 ECM Fan Control ECM Fan Motor Adjustments If the airflow needs to be increased or decreased see the A...

Reviews: