background image

Page 10 

                 

Installer’s Guide

NOTE: 

 The unit is shipped for horizontal installation.

NOTE:

 During heating operation, avoid supply air below 80  

degrees F or return air below 50 degrees F to prevent flue 

gas condensation.

Horizontal Airflow Units

1.  Location of the unit must allow service clearance around it 

to ensure adequate serviceability, maximum capacity, and 
peak operating efficiency.

 2.  These units are designed for outdoor installation. They  

may be installed directly on a slab, wood flooring, or on 
Class A, B, or C roof covering material. The discharge air 
from the condenser fans must be unrestricted for a minimum 
of 3 feet above the unit.

3.  The louvers above and below the flue hood in the side panel  

must have adequate clearance around the air opening into 
the combustion area. See Figure 2 on page 5 or Figure 4 on 
page 7.

4.  Examine all flue product-carrying areas of the furnace, its 

vent system, and the main burner for safe operation.

 

IMPORTANT:  

A minimum 0” clearance to combustible ma-

terial shall be maintained on air outlet duct.

5.  Exhaust vents or other sources of contaminated air must not 

be near the unit’s air inlet if outside air is to be introduced 
as make-up air or a ventilation feature is to be used. Con-
tamination from exhaust vents or chimneys may also foul the 
condenser causing degraded performance.

6.  Check the handling facilities to ensure the safety of person-

nel and the unit(s).

7.  The unit must be mounted level for proper drainage of water  

through the drain holes in the base pan.

8.  The unit should not be exposed to direct roof water runoff.
9.  Flexible duct connectors must be of a flame retardant 

material. All duct work outside of the structure must be  
insulated and weatherproofed in accordance with local 
codes.

10.  Holes through exterior walls or roof must be sealed in  

accordance with local codes.

11.  All fabricated outdoor ducts should be as short as possible.

Clearances

1.  The recommended clearances for single-unit installations 

are illustrated in Figures 1 to 6, pages 4-9.

2.  Any reduction of the unit clearances indicated in these 

figures may result in condenser coil starvation or the recir-
culation of warm condenser air.  Actual clearances, which 
appear to be inadequate should be reviewed with a local 
engineer.

3.  See the unit’s nameplate for the absolute minimum clear-

ance between the unit and any combustible surfaces. 
 

Down Airflow Units

1.  Location of the unit must allow service clearance around it to 

ensure adequate serviceability, maximum capacity, and peak 
operating efficiency. 

2.  Refer to the Installation section for instruction on converting 

the supply and return airflow covers to down airflow.

3.  The field assembled Roof Mounting Curb  (BAYCURB050A or 

BAYCURB051A) or a field fabricated curb should be in place 
before the unit is hoisted to the roof top.

 

The Roof Mounting Curb (frame) must be installed on a flat, 
level section of the roof (maximum of 1/4" per foot pitch) and  
provide a level mounting surface for the unit.  Also, be sure to 
provide sufficient height above the roof to prevent water from 
entering the unit.

4.  Be sure the mounting curb spans structural members (trusses) 

of the roof, thereby providing sufficient support for the weight of 
the unit, the curb, the duct(s), and any factory or field installed 
accessories.

5.  The unit must be mounted level for proper drainage of water 

through the drain holes in the base pan.

6.  Be sure the hole in the structure for the ducts is large enough 

to accommodate the fabricated ducts and the insulation sur-
rounding them. Flexible duct connectors must be of a flame 
retardant material. All duct work outside of the structure must be 
insulated and weatherproofed in accordance with local codes.

7.  Holes through exterior walls or roof must be sealed in accor-

dance with local codes.

8.  These units are designed for outdoor installation. They may be 

installed directly on a slab, wood flooring, or on Class A, B, or 
C roof covering material. The discharge air from the condenser 
fans must be unrestricted for a minimum of 3 feet above the 
unit.

9.  The louvers above and below the flue hood in the side panel 

must have adequate clearance around the air opening into the 
combustion area.

10.  Examine all flue product-carrying areas of the furnace, its vent 

system, and the main burner for safe operation.

 

IMPORTANT:

  A minimum 0” clearance to combustible material 

shall be maintained on air outlet duct.

11.  Exhaust vents or other sources of contaminated air should not 

be near the unit’s air inlet if outside air is to be introduced as 
make-up air or a ventilation feature is to be used. Contamination 
from exhaust vents or chimneys may also foul the condenser 
causing degraded performance.

12.  Check the handling facilities to ensure the safety of personnel 

and the unit(s).

Clearances

1.  The recommended clearances for single-unit installations are 

illustrated in Figures 1 to 6, pages 4-9.

2.  Any reduction of the unit clearances indicated in these fig-

ures may result in condenser coil starvation or the recircula-
tion of warm condenser air.  Actual clearances, which appear 
to be inadequate should be reviewed with a local engineer.

3.  See the unit’s nameplate for the absolute minimum clearance 

between the unit and any combustible surfaces.

Step 3—Review Location and Recommendation Information

Summary of Contents for 4DCZ6036

Page 1: ...erent hazards during installation and service the electrical supply must be disconnected and the main gas valve must be turned off If operating checks must be performed with the unit operating it is t...

Page 2: ...ingpressureexceedsthelimitofR 22 Proper service equipment is required Failure to use proper service tools may result in equipment damage or personal injury SERVICE Use only R 410A Refrigerant and appr...

Page 3: ...arefully before attempting to install oper ate or perform maintenance on this unit Installation and maintenance should be performed by qualified service techni cians only This unit is listed by Underw...

Page 4: ...Guide Step 2 Determine Unit Clearances Figure 1 4DCZ6036 1 of 3 Figures 1 through 6 show the unit critical dimensions NOTE The view labeled Bottom Side represents the Base as viewed looking up from u...

Page 5: ...Page 5 Installer s Guide Figure 2 4DCZ6036 2 of 3...

Page 6: ...Page 6 Installer s Guide Figure 3 4DCZ6036 3 of 3...

Page 7: ...Page 7 Installer s Guide Figure 4 4DCZ6048 through 4DCZ6060 1 of 3...

Page 8: ...Page 8 Installer s Guide Figure 5 4DCZ6048 through 4DCZ6060 2 of 3...

Page 9: ...Page 9 Installer s Guide Figure 6 4DCZ6048 through 4DCZ6060 3 of 3...

Page 10: ...fer to the Installation section for instruction on converting the supply and return airflow covers to down airflow 3 The field assembled Roof Mounting Curb BAYCURB050A or BAYCURB051A or a field fabric...

Page 11: ...clearance to combustible mate rial shall be maintained on air outlet duct Rooftop Installation Curb Mounting Convert Horizontal Airflow to Down Airflow The factory ships the unit for horizontal airflo...

Page 12: ...he unit by attaching clevis hooks pins or bolts to the unit casing casing hardware corner lugs angles tabs or flanges Failure to observe these warnings may result in equipment damage 1 Before preparin...

Page 13: ...r roof top applications using field fabricated ducts and sleeper rails rather than a curb or frame use the following procedure 1 Locate and secure the sleeper rails to the roof Three 3 sleeper rails a...

Page 14: ...drawing The manufacturer is not responsible for the unauthorized use of this drawing and expressly disclaims any liability for damages resulting from such unauthorized use Gasket Seal Spreader Bars B...

Page 15: ...rizontal Airflow Application with Frame Supply Air Return Air Roof Flashing Channel Iron Center Support Center Sup port required on all Frame Applications Angle Iron Frame Roof Flashing Return Air Ang...

Page 16: ...ise and vibration transmission Elbows with turning vanes or splitters are recommended to minimize air noise and resistance The first elbow in the ductwork leaving the unit should be no closer than two...

Page 17: ...making the gas pipe connection give serious consideration to providing the clearance necessary to remove the accesspanelsontheunit e g economizerandfilteraccesspanels NOTE In the absence of local cod...

Page 18: ...chonthegasvalveinletboss connect the gas piping to the unit Check the completed piping for leaks using a soap and water solution or the equivalent 6 After installation of the gas pipe in the unit the...

Page 19: ...Models that require 49 orifices for altitudes from 7000 8000 orifices must be changed to 50 HIGH ALTITUDE DERATE CHART NAT Altitude In Feet Inputs shown are with factory orifices 3 5 WC High Fire 1 8...

Page 20: ...ed A brief explanation of each mode follows RESTRICTED In the restricted mode of operation an outdoor temperature sensor is used to cause the unit to operate in the heat pump mode above a selected out...

Page 21: ...ns IMPORTANT Upon completion of wiring check all electrical connections including factory wiring within the unit Make sure all connections are tight Replace and secure all electrical box covers and ac...

Page 22: ...Page 22 Installer s Guide Figure 22 4DCZ6 Field Wiring Diagram 4DCZ6 FIELD WIRING DIAGRAM Y2 YL RD 2NDSTAGECOMPRESSOR 1STSTAGECOMPRESSOR CONSTANTCIRCULATION...

Page 23: ...h the compressor operating check the line voltage at the unit The voltage should be within the range shown on the unit nameplate If low voltage is encountered check the size and Step 5 Unit Startup le...

Page 24: ...ot been purged and air is trapped in the gas line NOTE Blue smoke produced by the heat exchanger during the initial burner firing is caused by a thin film of oil on the surface of the heat exchanger T...

Page 25: ...e After approximately 30 seconds the control energizes the indoor blower on high speed To maintain the indoor temperature at the desired setpoint the thermostat may operate the high fire gas heating c...

Page 26: ...fter defrost terminates when the outdoor coil should be clear of frost When the measured delta T during heating operation reaches the calculated initiate delta T the demand defrost control DFC opens t...

Page 27: ...he inside of the burners and the burner ports for deposit buildup and corrosion Wipe and brush the inside of the burner and the burner ports and then clean with a dry cloth If the deposit buildup or c...

Page 28: ...fast flashes is 3 seconds Status LED Liteport LED IGN Diagnostic Indicators Flash Codes Figure 23 ECM Fan Control ECM Fan Motor Adjustments If the airflow needs to be increased or decreased see the A...

Reviews: