background image

ALL phases of this installation must comply with NATIONAL, STATE AND LOCAL CODES

IMPORTANT —

This Document is 

customer property

 and is to remain with this unit.  Please return to service information

pack upon completion of work.

Installer’s Guide

Condensing Units

2TTA0030,040,050 & 060AD000A

These instructions do not cover all variations in
systems nor provide for every possible contingency to
be met in connection with installation.  All phases of
this installation must comply with NATIONAL, STATE
AND LOCAL CODES. 

 Should further information be

desired or should particular problems arise which are not
covered sufficiently for the purchaser’s purposes, the matter
should be referred to your installing dealer or local distributor.

A. GENERAL

The following instructions cover 2TTA0030,040,050 & 060AD
Condensing Units.

NOTE:
These outdoor units may be used with indoor units
equipped with Thermostatic Expansion Valve or Accutron™
Flow Control Check Valve (F.C.C.V.) assembly for refrigerant
flow control only.

Check for transportation damage after unit is uncrated.
Report promptly, to the carrier, any damage found to the unit.

To determine the electrical power requirements of the unit,
refer to the nameplate of the unit.  The electrical power
available must agree with that listed on the nameplate.

B. LOCATION & PREPARATION OF THE

UNIT

1. When removing unit from the pallet, notice the tabs on

the basepan. Remove tabs by cutting with a sharp tool as
shown in Figure 2 (see page 2).

2. The unit should be set on a level support pad at least as

large as the unit base pan, such as a concrete slab. If this
is not the application used please refer to application
bulletin 

SSC-APG002-EN

.

3. The support pad must NOT be in direct contact with

any structure.  Unit must be positioned a minimum of
12" from any wall or surrounding shrubbery to insure
adequate airflow.  Clearance must be provided in front
of control box (access panels) & any other side requir-
ing service access to meet National Electrical Code.
Also, the unit location must be far enough away from
any structure to prevent excess roof run-off water from
pouring directly on the unit. Do not locate unit(s) close
to bedroom(s).

4. The top discharge area must be unrestricted for at least

five (5) feet above the unit.

1

5. When the outdoor unit is mounted on a roof, be sure the

roof will support the unit’s weight.  Properly selected
isolation is recommended to prevent sound or vibration
transmission to the building structure.

6. The maximum length of refrigerant lines from outdoor to

indoor unit should NOT exceed sixty (60) feet.

7. If outdoor unit is mounted above the air handler,

maximum lift should not exceed sixty (60) feet (suction
line).  If air handler is mounted above condensing
unit, maximum lift should not exceed sixty (60) feet
(liquid line).

NOTE:
Refer to “Refrigerant Piping Software” Pub. No. 32-3312-02.

8. Locate and install indoor coil or air handler in accor-

dance with instruction included with that unit.

5 FT. ABOVE UNIT-UNRESTRICTED

18-AC51D5-5

Summary of Contents for 2TTA0030AD000A

Page 1: ...an Remove tabs by cutting with a sharp tool as shown in Figure 2 see page 2 2 The unit should be set on a level support pad at least as large as the unit base pan such as a concrete slab If this is no...

Page 2: ...ufficient size to allow both liquid and gas lines 5 Be sure the tubing is of sufficient length 6 Uncoil the tubing do not kink or dent 7 Route the tubing making all required bends and properly secure...

Page 3: ...l before opening the gas and liquid line valves 2 Attach appropriate hoses from manifold gauge to gas and liquid line pressure taps NOTE Unnecessary switching of hoses can be avoided and complete evac...

Page 4: ...sure Too Low Liquid Refrig Floodback TXV System Liquid Refrig Floodback Capillary Tube System I D Coil Frosting Compressor Runs Inadequate or No Cooling ELECTRICAL Compressor O D Fan Do Not Start Comp...

Page 5: ...grounding of equipment must comply with local codes 3 Low voltage wiring to be No 18 AWG minimum conductor 4 ODT B must be set lower than ODT A 5 If outdoor thermostats ODT are not used connect W1 to...

Page 6: ...28 3 4 724 28 1 2 651 25 5 8 7 8 3 8 137 5 3 8 65 2 5 8 210 8 1 4 57 2 1 4 457 18 2TTA0040AD 2 2 730 28 3 4 724 28 1 2 651 25 5 8 1 1 8 3 8 137 5 3 8 65 2 5 8 210 8 1 4 57 2 1 4 457 18 2TTA0050AD 3 1...

Page 7: ...18 AC51D5 5 7 Installer s Guide MOUNTING HOLE LOCATION Note All dimensions are in MM Inches NOTE For model base size see table on page 6 From Dwg 21D152989 Rev 0...

Page 8: ...X X X 6 Inform owner on how to operate system and what to expect of it At the same time deliver Owner s Use and Care Booklet CHECKOUT PROCEDURE After installation has been completed it is recommended...

Page 9: ...Instrucciones de Instalaci n 18 AC51D5 5 ES Unidad Condensadora 50 Hz 2TTA0030 040 050 060AD000A...

Page 10: ...2009 Trane...

Page 11: ...5 ES Informaci n General 4 Instalaci n de L neas de Refrigerante 5 Evacuaci n del Sistema 7 Conexiones El ctricas 8 Diagramas de Cableado en Campo 10 Dibujo Esquem tico 11 Datos Dimensionales 12 Proc...

Page 12: ...eral B UBICACION Y PREPARA CION DE LA UNIDAD 1 Al desmontar la unidad de la paleta observe las pesta as en la bandeja de base Retire las pesta as cort ndolas con un instrumento filoso como se muestra...

Page 13: ...gas siempre deber estar aislada PRECAUCION En aplicaciones de compresor tipo scroll la cabeza del compresor puede alcanzar altas temperaturas y provocar quemaduras severas No toque la cabeza del compr...

Page 14: ...de humedad en el puerto de la tapa de presi n al utilizar el trapo h medo SOLDADURADELASLINEASDE REFRIGERANTE 1 Retire la tapa de acceso a las v lvulas de servicio 2 Antes de soldar retire los tapones...

Page 15: ...de fugas evac e las l neas de refrigerante y el serpent n interior antes de abrir las v lvulas de las tuber as para l quido y gas 2 Acople mangueras adecuadas desde el m ltiple con man metros hasta la...

Page 16: ...bleado de energ a y la conexi n a tierra del equipo deben cumplir con los c digos locales F CONEXIONES ELECTRICAS En el caso de que los compresores scroll trif sicos fueran energizados con faseo inapr...

Page 17: ...r si se utilizara No cambie el Interruptor del Sistema de Termostato hasta haber aplicado la energ a durante una 1 hora Este procedimiento evitar disparos de sobrecarga del compresor durante su arranq...

Page 18: ...18AC51D5 5 ES 10 Diagramas de Cableado en Campo...

Page 19: ......

Page 20: ...18AC51D5 5 ES 12 Datos Dimensionales...

Page 21: ...apretado de todas las conexiones el ctricas 6 Observe el ciclo del ventilador exterior y verifique que gira libremente y opera sin obst culos 7 La tuber a de drenado del serpent n interior drena libr...

Page 22: ...rane mantiene una pol tica de cont nuo mejoramiento de sus productos y datos t cnicos se reserva el derecho de cambiar sus dise os y especificaciones sin previo aviso La instalaci n y labores de servi...

Page 23: ......

Page 24: ...iene una pol tica de cont nuo mejoramiento de sus productos y datos t cnicos se reserva el derecho de cambiar sus dise os y especificaciones sin previo aviso La instalaci n y labores de servicio al eq...

Reviews: