Storage Requirements for Chillers Not Yet Installed
D
Notice
Insulation Damage!
Direct exposure to sunlight may damage factory in-
stalled insulation. Failure to follow these instructions
could result in insulation damage.
Less than 1 month
1 – 6months
Greater than 6 months
Location requirements:
•
solid foundation
•
vibration free
•
dry
•
temperature range -40°F to 158°F (-40°C
to 70°C)
Location requirements:
•
solid foundation
•
vibration free
•
dry
•
temperature range -40°F to 158°F (-40°C
to 70°C)
Location requirements:
•
solid foundation
•
vibration free
•
dry
•
temperature range -40°F to 158°F (-40°C
to 70°C)
•
Do not remove any plastic coverings
•
Do not remove any plastic coverings
•
Do not remove any plastic coverings
•
Do not charge the chiller with refrigerant
•
If additional refrigerant is on site, follow
manufactures storage requirements
•
Do not charge the chiller with refrigerant
•
If additional refrigerant is on site, follow
manufactures storage requirements
•
Do not charge the chiller with refrigerant
•
If additional refrigerant is on site, follow
manufactures storage requirements
•
Verify dry nitrogen pressure using gauge
located on the evaporator shell reads 3 to
5 psig (21 to 34.5 kPa)
• Notify the local Trane office if charge has
escaped
•
Verify dry nitrogen pressure using gauge
located on the evaporator shell reads 3 to
5 psig (21 to 34.5 kPa)
• Notify the local Trane office if charge has
escaped
•
Verify dry nitrogen pressure using gauge
located on the evaporator shell reads 3 to
5 psig (21 to 34.5 kPa)
• Notify the local Trane office if charge has
escaped
•
Do not operate purge unit
•
Do not operate purge unit
•
Do not operate purge unit
•
Verify waterbox and tube bundles are
clean and dry
•
Verify waterbox and tube bundles are
clean and dry
•
Conduct an oil analysis and verify no oil
breakdown
•
Repeat yearly
•
Replace oil if breakdown has occurred
•
If no oil analysis program has been fol-
lowed, replace oil prior to start up
•
Every 6 months start the oil pump and
rotate compressor shaft 450 degrees to
prevent bearing issues
• Contact your local Trane office to preform
this task
Note: Chillers stored 5 years or longer should be inspected every 5 years by a qualified service organization for leaks.
(a) If protective plastic coverings need to be removed for access and/or service, contact your local Trane office.
10