CVHE-SVX005B-EN
11
N
No
otte
e:: The chiller should remain within its protective
shrink-wrap covering during storage.
Type of Requirement
Trane Supplied
Trane Installed
Trane Supplied
Field Installed
Field Supplied
Field Installed
Foundation
•
Meet foundation requirements
Rigging
•
Safety chains
•
Rigging shackles
•
Lifting beam
Disassembly/Reassembly
(as required)
•
Trane will perform or have
direct on-site supervision
of the disassembly and
reassembly work (contact
your local Trane office for
pricing)
Isolation
•
Isolation pads or spring
isolators
•
Isolation pads or spring isolators
•
Optional spring isolators, when required, are
installed by others; do NOT overload springs and do
NOT install isolation springs if they block serviceable
parts such as the oil tank system, service valves,
etc.
Electrical
•
Circuit breakers or fusible
disconnects (optional)
•
Unit-mounted starter
(optional)
•
Power factor correction
capacitors (PFCCs)
(optional)
•
Jumper bars
•
Temperature sensor
(optional outdoor air)
•
Flow switches (may be
field supplied); for
installation instructions
for the ifm efector
®
flow
detection controller and
sensor, refer to
Flow Detection
Controller and
Sensor,” p. 31
or Trane
literature that shipped
with the device
•
Remote-mounted
starter (optional)
•
Air-Fi
®
wireless
communication
(optional)
•
Wi-Fi wireless
communication
(optional)
•
Circuit breakers or fusible disconnects (optional)
•
Electrical connections to unit-mounted starter
(optional)
•
Electrical connections to remote-mounted starter
(optional)
•
Wiring sizes per submittal and National Electric Code
(NEC)
•
PFCCs (remote mounted starter optional only)
•
Terminal lugs
•
Ground connection(s)
•
Jumper bars
•
BAS wiring (optional)
•
Inter-processor communication (IPC) wiring (AFD
and remote-mounted starters only)
•
Control voltage wiring (AFD and remote-mounted
starters only)
•
Oil pump interlock wiring (AFD and remote mounted
starters only)
•
High condenser pressure interlock wiring (AFD and
remote-mounted starters only)
•
Chilled water pump contactor and wiring including
interlock
•
Condenser water pump contactor and wiring
including interlock
•
Option relays and wiring
•
Symbio 800 BAS communication wiring (optional)
Water piping
•
Flow sensing devices
(may be field supplied)
•
Taps for flow sensing devices
•
Taps for thermometers and gauges
•
Thermometers
•
Strainers (as required)
•
Water flow pressure gauges
•
Isolation and balancing valves in water piping
•
Vents and drain on waterbox valves (one each per
pass)
•
Pressure relief valves (for waterboxes as required)