Run the oil pump to verify pump can provide
18 to 22 psid (124.1 to 151.7 kPaD) net
pressure.
☐
Verify and record control parameters.
☐
Verify all control interlocks are installed and
properly functioning.
☐
Set AFD grounding jumpers (PE-A for MOV
and PEB for Common Mode) for power
distribution grounding:
☐
Both jumpers “Connected” for Solidly
Grounded System (Center Ground Wye).
☐
Both jumpers “Disconnected” for Non
Solidly Grounded System (Any Delta,
High Impedance Ground, or
Ungrounded Wye).
N
No
otte
e:: Refer to AFD-SVG002*-EN for more
information.
☐
Dry run starter (non-Adaptive Frequency
™
Drive [AFD]).
☐
Measure condenser pressures and flow.
☐
Adjust condenser flow sensing device.
☐
Measure evaporator pressures and flow.
☐
Adjust evaporator flow sensing device.
☐
Measure optional heat recovery pressures and
flow.
☐
Adjust optional heat recovery flow sensing
device.
☐
Inspect motor starter panel and perform starter
panel checkout procedures.
☐
Confirm proper phase check incoming power.
☐
Inspect control panel.
☐
Apply separate source 120 Vac power to control
to perform control panel checkout procedure.
☐
Review and record unit configuration
parameters.
☐
Confirm oil pump pressure—regulating valve
setting.
☐
Verify vane operator is working properly and
moves without binding.
☐
Dry run test starter (non-AFD).
☐
Remove separate source power and reconnect
wiring.
☐
Install optional Air-Fi and/or Wi-Fi modules.
3. P
Prre
ep
pa
arra
attiio
on
n ffo
orr S
Stta
arrtt--u
up
p
☐
Relieve nitrogen holding charge.
☐
Evacuate and charge the system.
☐
Apply power to the starter panel.
☐
Verify current to the oil sump heater.
4. C
Ch
hiilllle
err S
Stta
arrtt--u
up
p
☐
Set Purge mode to “On.”
☐
Bump-start the compressor and verify
compressor motor rotation.
☐
Start chiller.
☐
Verify no unusual noises or vibrations and
observe operating conditions.
☐
If necessary, adjust oil pressure regulator
between 18 to 22 psid (124.1 to 151.7 kPaD) net.
☐
Measure and verify refrigerant pump pressure.
☐
When chiller is stable, take system log three
times at 15-minute intervals.
☐
Set Purge mode to “Adaptive.”
☐
Reset the “Starter Energy Consumption”
resettable.
☐
Record a
Chiller Service Report
.
☐
Review “AdaptiView Display Customer Training
Checklist.”
☐