40
8.4.3.5 Evaporator coil temperature protection
TEstop
T2
Resume
Off
Decrease
TEdown
TEnorm
Hold
Off: Compressor stops.
Decrease: Decrease the running frequency to the lower level.
Hold: Keep the current frequency.
Resume: No limitation for frequency.
8.4.4 Auto-mode
This mode can be chosen with remote controller and the setting temperature can be changed between
17~30
℃
.
In auto mode, the machine will choose cooling, heating or fan-only mode according to
Δ
T (
Δ
T =T1-Ts).
Δ
T=T1-Ts Running
mode
Δ
T
>
1
℃
Cooling
-1<
Δ
T
≤
1
℃
Fan-only
Δ
T
≤
-1
℃
Heating
Indoor fan will run at auto fan of the relevant mode.
The louver operates same as in relevant mode.
If the machine switches mode between heating and cooling, the compressor will keep stopping for 15
minutes and then choose mode according to T1-Ts.
If the setting temperature is modified, the machine will choose running function again.
8.4.5 Drying mode
8.4.5.1 Indoor fan speed is fixed at breeze and can’t be changed. The louver angle is the same as
in cooling mode.
Summary of Contents for TPG A128 IVP
Page 11: ...11 5 Wiring Diagram 5 1 Indoor Unit TPN A128 IVP TPN A135 IVP TPN A180 IVP TPN A240 IVP...
Page 12: ...12 5 2 Outdoor Unit TPGA128IVP TPG A135 IVP TPG A180 IVP...
Page 13: ...13 TPG A240 IVP...
Page 46: ...46 9 2 2 Indoor unit and outdoor unit communication protection error diagnosis and solution E1...
Page 50: ...50 9 2 7 Outdoor fan speed has been out of control diagnosis and solution F5...
Page 51: ...51 9 2 8 IPM malfunction or IGBT over strong current protection diagnosis and solution P0...
Page 52: ...52 9 2 9 Over voltage or too low voltage protection diagnosis and solution P1...
Page 53: ...53 9 2 10 Inverter compressor drive error diagnosis and solution P4...