Defrosting action
:
For
TPN A128 IVP
+
TPG A128 IVP
,
TPN A135 IVP
+
TPG A135 IVP
Compressor
on
off
on
on
on
off
off
off
4-way valve
Outdoor fan
Indoor fan
Indoor fan breeze(10s)
xx
10s
no longer than 10m
30s
FrequencyF16
10s
Frequency F3
xx=60
For
TPN A180 IVP
+
TPG A180 IVP,
TPN A240 IVP
+
TPG A240 IVP
Compressor
on
off
on
on
on
off
off
off
4-way valve
Outdoor fan
Indoor fan
Indoor fan breeze(10s)
xx
no longer than 10m
Frequency F16
30s
10s
10s
Frequency F3
xx=90