48
g) Strong
mode
:
:
:
:
In strong mode, when the unit is in cooling, heat, or auto mode, indoor fan speed will work in high flow mode,
will change to set air flow speed after 15 minutes, during this 15 minutes, the air flow speed can not be
changed.
h) Timer
on
:
:
:
:
The air conditioner can be set the start-up time at 1-24 hours later.
The start-up function should be set in operation mode.
After setting, the air conditioner shut down immediately, the operation light (green) is off, the timer light is on.
i) Sleep
mode
:
:
:
:
This function can be set shut-down after 1
、
2
、
3
、
4
、
5
、
6
、
10 hours, the air conditioner will shut down automatically
as the indication.
j) Indoor fan auto air speed control:
When the air flow is set as auto mode, the indoor fan speed is control as following chart:
7. Other control:
1) Swing louver control
Only if the indoor fan runs, the swing louver control works.
2) The buzzer control
The controller start or receive the proper signal from the remote controller, the buzzer will short buzz once.
Special
:
a
.
Forcible: three short buzz
b
.
Power on: two short buzz
c
.
Power off: a long buzz.
9. Protection
:
:
:
:
a) Compressor
delay
protection
There will be a 3 minutes interval before the restarting of the unit.
b)
Indoor anti frosting protection
In cooling and dehumidifying mode, after the compressor works for 10 minutes, if indicates that Te
≤
°C, and this
situation last for 20 seconds, the compressor and outdoor fan will stop, only if Te = 7°C , the unit restarts
automatically, and goes into the pre mode.
c)
Indoor anti super heat protection
In heat mode, when it indicates Te
≥
58°C, outdoor fan stops, when Te
≤
47°C, the outdoor fan restart to work.
When it indicates Te
≥
65°C, and this situation last for 10 minutes, the compressor stops.
Mode Heat
Cooling
Fan
High Mid
Lo Stop
Ta
-4 -2
▲
▲
+2 +4
▲
+2 +4