Note: The factory settings of the
single menu points are marked
with
in this manual.
Status display
Diagnosis
status display
for inputs as photocell, safety sensing edges, stop button, impulse switch ....
I
impulse switch
P
partial opening switch
C
CLOSE-switch
S
STOP-switch
Pi
photocell inside
Po
photocell outside
1
safety edge main closing edge 1
2
safety edge main closing edge 2
Delete position
Diagnosis
NO:
no deleting of end positions “gate closed” and “gate
open”
YES:
the determined end positions are being deleted.
Note: the end positions are being newly determined
after impulse.
Factory setting
Diagnosis
NO:
no reset to factory setting
YES:
reset to factory setting
Software version
Diagnosis
shows the software version and the operator type on the text display
Serial number
Diagnosis
shows the serial number on the text display
All inputs OK.
e.g.
Diagnosis
Connections and adjustments
The mechanical stops have to be placed so
that possibly existing safety contact edges
can not be triggered, as this would lead to
an error message.
$$$$$$$$$$$$$$$$
$$$$$$$$$$$$$$$$
I P C S Pi Po 12
$$$$$$$$$$$$$$$$
$$$$$$$$$$$$$$$$
I P C S Pi Po 12
- - x-
Impulse-, pedestrian - and close button not triggered.
STOP-button and photocell inside are triggered.
Photocell outside not triggered.
Safety sensing edge 1 not connected or defect.
Safety sensing edge 2 triggered.
$
Status: not triggered
$
-
Status:
triggered
$
x
Status: contact strip not connected or defect
$
o
Status: contact strip or photocell deactivated in menu