SWING GATE OPERATOR USER’S MANUAL
20
Flashing light (See Fig.25)
Attach two wires of flashing light to port ‘LAMP’.
Fig.25
Electric lock DC12V (see Fig.26)
Connect two wires of electric lock to port ‘LOCK’. Wire size should be more than 1 mm
2
.
Limit switch (see Fig.26)
Connect primary limit switch that on primary gate operator (installed on primary gate with electric
lock) to port ‘OP1’, ‘COM’, ‘CL1’.
Connect secondary limit switch to port ‘OP2’, ‘COM’, ‘CL2’.
Fig.26
Note: Use operator with single
gate, connect motor to ‘U1’, ‘V1’, ‘W1’, connect limit switch to
‘OP1’, ‘COM’, ‘CL1’, it is important to short the ‘OP2’ and ‘COM’, ‘CL2’ and ‘COM’ terminal
with the jumper wires. See Fig.27
.
Fig.27
COM
OP1
LOCK
X5
CL1
OP2
COM CL2
Electric
lock
open
com
close
close
com
open
Connection of electric lock & limit switch
Primary limit switch
Secondary limit switch
Power supply
Connection of motor & flashing light
X1
E
N
L
Earth Neutral Power
X2
U1
V1
W1
U
V
W
W
V
U
W2
V2
U2
X3
Primary Motor
Secondary Motor
LAMP
X4
Flashing light
Ground
Terminal 'E' on primary
gate operator see Fig.16
Terminal 'E' on secondary
gate operator see Fig.16
COM
OP1
LOCK
X5
CL1
OP2
COM CL2
Limit switch
open
com
close
X2
U1
V1
W1
U
V
W
Motor
For single gate
Short circuit