Vapor Eliminator Trouble Shooting
PROBLEM: Product is flowing from the Vapor Eliminator vents
A) Foreign matter located in between seal plate o-rings and metal reeds.
B) The valve plate may be worn, requiring replacement.
C) The float may have been punctured not allowing the float to rise and seal the air vents.
D) The float may have been ruptured from a surge of pressure within the system.
E) The metal reeds may be fatigued and require replacement.
F) The metal reeds may be out of alignment with the seal plate.
PROBLEM: The meter is still registering vapor within the system
A) The vapor return line is not the required minimum of 1/2‖ ID.
B) Cavitating pump or leaking pump/valve seals.
Differential Valve Trouble Shooting
PROBLEM: Valve fails to open
A) Damaged vapor return line with no pressure relief from Valve Cap (Bonnet)
B) Puncture or Tear in Valve Diaphragm
PROBLEM: Product continues to flow through valve
A) Valve Seat has excessive wear or is damaged.
B) Valve Poppet is not secure and requires tightening.
C) Faulty Solenoid Valve (foreign material or ice).
Summary of Contents for 700-LP Series
Page 10: ...Page 10 Meter Dimensions in Inches Millimeters...
Page 14: ...Page 14 700 20 LP Meter Assembly...
Page 16: ...Page 16 730 20 LP Vapor Eliminator Assembly...
Page 18: ...Page 18 720 20 LP Strainer Assembly...
Page 20: ...Page 20 757 20 LP Differential Valve Assembly...
Page 22: ...Page 22 782 20 LP In Line Check Assembly...
Page 45: ...Page 45 Page 45 NOTES...
Page 46: ...Page 46 Page 46 NOTES...