40
Ethernet module User’s Manual
Chapter 4 Preparing for Operation (Software)
4
(2) Functions
• For the EN311, this is the function block to request module control, TCP/IP protocol,
and/or UDP/IP protocol communication.
• When an execution request(REQ) becomes TRUE(ON) from FALSE(OFF), the N
number of transmit data words will be routed from transmission data P with the
contents of the specified transmission command (CMD).
• The number of transmission data words, 1-1000 can be specified (It depends on the
socket service command).
• When the transmission completes, the completion output(DONE) becomes TRUE(ON)
for one scanning time and the corresponding socket number is displayed on the
STATUS.
• When the transmission ends with an error, the error(ERROR) becomes TRUE(ON) for
one scanning time and the error status(error description) is displayed on the STATUS.
The completion output (DONE) does not turn ON if an error occurs.
Socket Service Commands used by USED_T
Description
Command
Reset request
16#0311
Parameter setup request
16#0312
Operating mode control request
16#0313
Remote station verification request
16#0314
Time set request
16#0318
Router IP address set request
16#0319
PC link (Register write request)
16#0321
UDP open request
16#0331
UDP send request/Broadcast transmission
16#0332
UDP close request
16#0334
TCP open request
16#0335
TCP send request
16#0337
TCP close request
16#0339
Summary of Contents for V Series
Page 1: ...6F8C0904 Integrated Controller V Series Ethernet module EN311 User s Manual Sep 30 2004 ...
Page 12: ......
Page 16: ......
Page 34: ......
Page 40: ......
Page 106: ......
Page 180: ......
Page 199: ...6F8C0904 179 7 5 RAS Information Readout 7 Figure 7 1 Packet Format IP Datagram ...
Page 200: ...180 Ethernet module User s Manual Chapter 7 RAS Information 7 ...
Page 224: ......
Page 240: ......
Page 244: ......
Page 248: ......
Page 250: ......
Page 256: ......
Page 258: ......