218
Ethernet module User’s Manual
Appendix C Error Status Table
C
0BxxH
Transmission error
• Occurs if the EN311 detects an error and responds.
For more information, see Table C.2 below.
Table C-2 Detailed Information
Error
Code
Description
Normal
completion
01H
Local station fault
02H
The local station is in down mode
Local station
standby
03H
Data transmission in standby mode was requested.
Timeout
20H
Timeout occurred during TCP open processing or receive
processing, or during UDP receive processing.
Length error
30H
Incorrect transmission data length
Station mode
error
40H
One of the following requests was issued in a mode other than
standby mode:
a. Parameter setup,b. MAC address setup,c. Reset
MAC/IP not set up
50H
Occurs if the MAC address or IP address is not set up.
Transmission
prohibited state
60H
• Occurs if a PC link request was issued in run mode in the mes-
sage transmission prohibited state.
• Occurs if a socket open, close, send, or receive request is
issued in run mode in the socket interface transmission prohib-
ited state.
Format error
70H
Occurs when there is a format error in the request text.
71H
Port number error/IP address error
72H
Request code error
73H
Time setting: Year
74
H
Time setting: Month
75H
Time setting: Day
76
H
Time setting: Hour
77H
Time setting: Minute
78
H
Time setting: Second
Opened
80H
Occurs if an open request is issued for an already open socket.
Unopened
81H
• Occurs if send, receive, or close request is issued for an
unopened socket.
• The TCP socket was used to make the transmit/receive request
to the socket that is receiving CLOSE from the remote station.
Incorrect socket
identifier
82H
Occurs if the socket identifier is out of range (1 to 8).
Incorrect control
request
specification
83H
Occurs if a request that was prohibited by an operating mode
control request is issued.
• Occurs if a run request is issued in run mode.
• Occurs if a standby request is issued in standby mode.
• Occurs if a run request and a standby request are issued at the
same time.
Table C-1 Contents of Completion Statuses
STATUS
Name
Explanation
Summary of Contents for V Series
Page 1: ...6F8C0904 Integrated Controller V Series Ethernet module EN311 User s Manual Sep 30 2004 ...
Page 12: ......
Page 16: ......
Page 34: ......
Page 40: ......
Page 106: ......
Page 180: ......
Page 199: ...6F8C0904 179 7 5 RAS Information Readout 7 Figure 7 1 Packet Format IP Datagram ...
Page 200: ...180 Ethernet module User s Manual Chapter 7 RAS Information 7 ...
Page 224: ......
Page 240: ......
Page 244: ......
Page 248: ......
Page 250: ......
Page 256: ......
Page 258: ......