![Toshiba V Series User Manual Download Page 65](http://html.mh-extra.com/html/toshiba/v-series/v-series_user-manual_424936065.webp)
6F8C0904
45
4.4 Function Block Specifications for EN311 Control
4
Table 4-3 Detailed Information
Error
Code
Description
Normal complete
01H
Local station fault
02H
The local station is in down mode
Local station standby
03H
In standby mode, data transmission was requested.
Timeout
20H
Timeout occurred during TCP open/receive processing, or
during UDP receive processing.
Length error
30H
Incorrect send data length
Station mode error
40H
One of the following requests was issued in a mode other
than standby mode:
a. Parameter setup, b. MAC address setup, c. Reset
MAC/IP not set up
50H
Occurs if the MAC address or IP address is not set up.
Transmission
prohibited state
60H
• Occurs if a PC link request was issued in run mode in the
message transmission prohibited state.
• Occurs if a socket open, close, send, or receive request
is issued in run mode in the socket interface transmission
prohibited state.
Format error
70H
Occurs when there is a format error in the request text.
71H
Port number error/IP address error
72H
Request code error
73H
Time setting: Year
74H
Time setting: Month
75H
Time setting: Day
76H
Time setting: Hour
77H
Time setting: Minute
78H
Time setting: Second
Already opened
80H
Occurs if an open request is issued for an already open
socket.
Unopened
81H
• Occurs if send, receive, or close request is issued for an
unopened socket.
• Occurs if transmitted to/received by the socket which has
received a close request from the remote station with the
TCP socket.
Incorrect socket
identifier
82H
Occurs if the socket identifier is out of range (1 to 8).
Incorrect control
request specification
83H
Occurs if a request that was prohibited by an operating
mode control request is issued.
• Occurs if a run request is issued in run mode.
• Occurs if a standby request is issued in standby mode.
• Occurs if a run request and a standby request are issued
at the same time.
Summary of Contents for V Series
Page 1: ...6F8C0904 Integrated Controller V Series Ethernet module EN311 User s Manual Sep 30 2004 ...
Page 12: ......
Page 16: ......
Page 34: ......
Page 40: ......
Page 106: ......
Page 180: ......
Page 199: ...6F8C0904 179 7 5 RAS Information Readout 7 Figure 7 1 Packet Format IP Datagram ...
Page 200: ...180 Ethernet module User s Manual Chapter 7 RAS Information 7 ...
Page 224: ......
Page 240: ......
Page 244: ......
Page 248: ......
Page 250: ......
Page 256: ......
Page 258: ......