Appendix C Error Status Table
Tables C.1 and C.2 list the contents of the error status generated from STATUS at the
completion of USEND_T/URCV_T function block.
Table C-1 Contents of Completion Statuses
STATUS
Name
Explanation
0
Normal completion
-5001
Parameter error
• Occurs if a slot number other than 03xxH is specified.
• Occurs if a non-existent command number is specified
in a USEND_T/URCV_T function block.
• Occurs if a value other than 1 to 8 is specified for the
socket identifier.
• Occurs if an incorrect parameter is specified in a RAS
information readout request.
-5002
Transmission
complete timeout
• Occurs if an S3 internal timer times out when issuing
one of the following commands:
UDP open, UDP send, UDP close, TCP send, TCP
close
-5051
Register specification
error
• In a register read request, a register type not valid for
the local station register (except D and SW) is specified.
-5071
Register specification
error
• In a register write request, a register type not valid for
the remote station register (except D and SW) is speci-
fied.
-5052
Response timeout
• Occurs if a response is not received within the specified
time for a register read/write request.
-5054
Memory write protect
error
• In a register read request, a SW register is specified for
the reception data storage area of the local station.
-5074
Memory write protect
error
• In a register write request, a SW register is specified for
the data storage area of the remote station.
-5057
No send channel
• Occurs if the corresponding EN311 is not installed.
-5058
Reserved
-5059
Incorrect transmission
word count
• Occurs if either 0 or 1001 words or more were specified
for a UDP/TCP socket send/receive request.
-5060
Boundary error
• Occurs if the specified data storage area does not exist
on the S3 in case of the following commands:
RAS information readout, UDP send/receive, TCP
send/receive, register read/write
-5080
Boundary error
• Occurs if the specified data storage area does not exist
on the S3 in case of the following command (occurred
in the remote station):
Register write
-5062
No I/O response
• Occurs if a command is issued when the S3 cannot
access the EN311.
-5064
Send data capacity
exceeded
• Occurs if a transmission is repeated to a non-existent
remote station with a rapid cycle.
-5050
Error during reset
• Occurs if another command is issued during a reset
request execution.
Summary of Contents for V Series
Page 1: ...6F8C0904 Integrated Controller V Series Ethernet module EN311 User s Manual Sep 30 2004 ...
Page 12: ......
Page 16: ......
Page 34: ......
Page 40: ......
Page 106: ......
Page 180: ......
Page 199: ...6F8C0904 179 7 5 RAS Information Readout 7 Figure 7 1 Packet Format IP Datagram ...
Page 200: ...180 Ethernet module User s Manual Chapter 7 RAS Information 7 ...
Page 224: ......
Page 240: ......
Page 244: ......
Page 248: ......
Page 250: ......
Page 256: ......
Page 258: ......