Unified Controller Vm series TC-net 100(TNB) Module Manual
73
A.2 TC-net 100 Transmission Specifications
Table A-3
TC-net 100 transmission specifications
Item
Specification
Media access method
DOMA(Deterministic Ordered Multiple Access) method
Data transmission speed
100Mbps
Topology
Star
Transmission path
Single bus
Redundant bus
Connector
MT-RJ optical connector
Cable length
Up to 2km
(It can be up to 8km when using laser-emitting diode in
optical fiber single mode.)
Node count
Up to 254 nodes/system
(including optical shared hub UTNH21A)
HUB count
Cascade, 5 stages
Transmission mode
Scan transmission
High-speed cycle
:
1ms to 160ms
Medium-speed cycle
:
2ms to 1,000ms
Low-speed cycle
:
2ms to 10,000ms
Scan transmission capacity
128KW
/
system (16bits/word)
2048 blocks/system (64W/block)
Transmission capacity 576 blocks/node (36KW/node)
(High
:
64, Medium
:
128, Low
:
384)
State
change
detection
Change
detection
words
128W/node
Change
detection
cycle
Change
detection
words
×
30
μ
s
Detection
signal
interval
50ms
or
more
Interface
Optical
MT-RJ type connecter
Cable
Optical
Quartz GI cable(62.5/125, long wave) and (50/125 long
wave)
Summary of Contents for TNB21
Page 1: ...Unified Controller Vm Series TC net 100 TNB Module Instruction Manual 6F8C1637 ...
Page 14: ...6F8C1637 xii ...
Page 28: ...Chapter 2 Installation and Wiring 6F8C1637 14 ...
Page 62: ...Chapter 3 Setting 6F8C1637 48 ...
Page 65: ...51 Chapter 5 Troubleshooting This chapter describes troubleshooting for the TNB Module ...
Page 82: ...Chapter 7 Application Interface 6F8C1637 68 ...
Page 85: ...Unified Controller Vm series TC net 100 TNB Module Manual 71 ...
Page 90: ...75 Appendix B Outside Dimensions ...
Page 92: ...77 Appendix C Related Products ...
Page 94: ...79 Appendix D Decimal hexadecimal Conversion Table ...
Page 97: ...Appendix D Decimal hexadecimal Conversion Table 6F8C1637 82 ...
Page 99: ...1637 0 1912 ...